NEC Article 430 Part VII covers

Art. 430, Part VII provides the requirements for motor controllers. The requirements for motor control circuits are in Part VI. What’s the difference? Part VI is about the supply power to motor controllers. The intention of Part VII is to require suitable controllers for all motors [430.81].

Controllers for smaller motors have special requirements:

  • Stationary motor of 1/8 horsepower or less. These are things such as clock motors. The branch circuit disconnecting means can serve as the controller [430.81(A)].
  • Portable motor of 1/3 horsepower or less. The controller can be a cord connector or an attachment plug and receptacle [430.81(B)].

A controller must be capable of:

  • Starting the motor;
  • Stopping the motor; and
  • Interrupting the locked-rotor current of the motor [430.82(A)].

Additional requirements apply to autotransformers [430.82(B)] and rheostats [430.82(C)]. A controller doesn’t need to open all conductors to a motor [430.84] unless it also serves as a disconnecting means [Exception].

The requirements for controller ratings are a bit confusing. Begin with the general rule: The horsepower rating of the controller can’t be lower than the horsepower rating of the motor [430.83(A)(1)]. Then look through the special cases to see if you are working with one of those:

  • Branch-circuit inverse time breaker rated in amperes. If it’s also used for overload protection, it must conform to the Art. 430 provisions governing overload protection.
  • Molded case switch rated in amperes. You can use it as a controller, even though it’s not rated in horsepower and can’t conform to the general rule.
  • The smaller motors covered above (e.g., clock motors).
  • Torque motors. The controller must have a continuous-duty, full-load current rating not less than the nameplate current rating of the motor [430.83(D)].
  • Controller with a voltage rating. It must match the nominal voltage between any two conductors if a straight rating. If it has a slash rating, the nominal voltage to ground from any conductor cannot exceed the lower of the two ratings [430.83(E)].

Each motor must be provided with its own controller [430.87], but there are four exceptions.

Adjustable speed motors can’t be started under a weakened field unless the motor in question is designed for such starting [430.88]. Speed limiting is required for three types of motors or machines, for example series motors, and there are two exceptions [430.89].

If you use a combination fuseholder and switch as a controller, the fuseholder must accommodate the size of fuse specified in Art. 430, Part III for motor overload protection.

I. General

This article covers requirements for motors, motor branch circuit and feeder conductors and their protection, motor overload protection, motor control circuits, motor controllers, and motor control centers. There are general and specific requirements. Figure 430.1 in the NEC® describes where in Article 430 different parts of the circuits are covered as well as other articles. This article does not cover air-conditioning and refrigeration equipment, which is covered in Article 440 and motor control centers which is covered in 110.26(F).

430.2

Definitions

430.4

Part Winding Motors

430.5

Other Articles

There are numerous other articles with which motor and controllers must comply for special cases. These are noted in Table 430.5.

430.6

Ampacity and Motor Rating Determination

Generally, the conductor size is determined by using the allowable ampacity tables as noted in Section 310.15(B) or calculated as noted in Section 310.15(C). Use Section 400.5 to determine flexible cord conductor size.

(A) General Motor Applications. Tables 430.147 through 430.150 are used to determine ampere rating for sizes of wire, switches, circuit protection, and the like (not the nameplate ratings). If the motor has a marking in amperes but not horsepower, it is assumed that the horsepower ratings correspond to those in Tables 430.247 through 250. Motors with speeds less than 1200RPM and high-torque motors can have higher full load currents. Multispeed motors have full load currents that vary with speed. In these cases, use the nameplate current ratings. There are three exceptions. Separate motor overload protection is based on the nameplate reading.

(B) Torque Motors. The rated current to be used for these motors is the locked-rotor current. This nameplate value is used to determine the size of the branch circuit conductors as noted in Sections 430.22 and 430.24, the rating of the overload protection, and the rating of the motor overload protection and the rating of the branch circuit short circuit and ground fault protection.

(C) Alternating Current Adjustable Voltage Motors. For these types of motors use the maximum operating current marked on the motor. If there is no marking, then use 150% of the values in Tables 430.149 and 430.150.

430.7

Marking on Motors and Multimotor Equipment

430.8

Marking on Controllers

430.9

Terminals

430.10

Wiring Space in Enclosures

Table 430.10(B) indicates the minimum wire bending space at the terminals of enclosed motors.

430.11

Protection against Liquids

430.12

Motor Terminal Housings

Tables 430.10(B), 430.12(B), 430.12(C)(1), and 430.12(C)(2) give various dimension and space requirements. There is also information on connections.

430.13

Bushing

430.14

Location of Motors

430.16

Exposure to Dust Accumulations

430.17

Highest-Rated or Smallest-Rated Motor

If this is to be determined for compliance with Sections 430.24, 430.53(B), and 430.53(C), use the rated full-load current from Tables 430.147, 430.148, 430.149, and 430.150.

430.18

Nominal Voltage of Rectifier Systems

II. Motor Circuit Conductors

The rules of this part apply to circuits supplying motors at 600 V or less.

Generally size conductors at 125% of the motor full-load rated current as noted in Section 430.6(A)(1) for the supply to a single motor rated for continuous duty. There is an exception to this rule. It is for direct-current motors that operate from a single-phase power supply which is rectified. There are regulations for multispeed motors and wye-start delta-run motors and part winding motors. When the junction box is allowed to be separated from the motor, a special exception is made for wire size on motors of 1 hp or less. There are provisions for other than continuous-duty motors.

430.23

Wound-Rotor Secondary

The secondary leads for a continuous-duty wound-rotor motor must be rated at least 125% of the full-load secondary current. If the motor is not continuous, Table 430.22(E) must be used. Table 430.23(C) is used when the secondary resistor is separate from the controller.

430.24

Several Motors or a Motor(s) and Other Load(s)

In this case the conductors are rated at 125% of the full load current of the largest motor (the same as a single motor) plus the full-load current of all additional motors plus the ampere rating of the other loads which are calculated in accordance with Article 430.6(A) and other sections of the NEC®. There are three exceptions: continuous-duty, motor-operated fixed space heating, and interlocked motors.

430.25

Multimotor and Combination-Load Equipment

The conductors for these loads are based, as a minimum, on the circuit ampacity marked on the equipment in accordance with Section 430.7(D). If the equipment is not factory wired, and the nameplates visible as per Section 430.7(D)(2), the conductors are calculated in accordance with Section 430.24.

430.26

Feeder Demand Factor

If all motors will not operate simultaneously for any number of reasons, the authority having jurisdiction can allow the use of a demand factor.

430.27

Capacitors with Motors

430.28

Feeder Taps

Feeder tap conductors must be sized at least according to Part II of this section and either be enclosed and 3.0 m (10 ft.) or less in length or be one-third or more of the rating of the feeder, 7.5 m (25 ft.) or less in length, and protected or have an ampacity not less than the feeder conductors. There is an exception for feeder taps over 7.5 m (25 ft.) in high bay manufacturing buildings. There are additional rules.

430.29

Constant-Voltage DC MotorsPower Resistors

III. Motor and Branch-Circuit Overload Protection

The overload protection is usually the thermal overloads in the controller or starter. It should not be confused with the short-circuit protection, which is the fuse or circuit breaker in the panelboard. Diagram 430.1 in the Code should be referred to, as well as Annex D, Example No. D8.

430.32

Continuous-Duty Motors

There are four methods acceptable:

(A) More than 1 Horsepower

1. A separate overload device must be used. It must be rated at not more than 125% of the motor nameplate rating if the motor is rated with a temperature rise of not more than 40°C or a service factor of 1.15 or more. The rating is reduced to 115% for all other motors. Exceptions are provided in Section 430.32(C).

2. Thermal protectors as part of the motor are listed in this paragraph.

3. If the motor is part of an approved assembly, will not normally have overloads, and has some protection against failure to start, additional overload protection is not necessary.

4. Motors larger than 1500 hp are discussed in this paragraph.

(B) One Horsepower or Less, Automatically Started. Here again there are four acceptable methods; the first three are similar to the first three for motors rated more than 1 hp. These include separate devices (ratings are indicated), thermal protectors, and cases where no additional protection other than branch-circuit protection is required (where protection is integral with the motor). A fourth case is that where the impedance of the motor protects against overheating when the motor does not start.

(C) Selection of Overload Relay. In the event the ratings chosen as listed in Section 430.32(a)(1) and (c)(1) will not allow the motor to start, this section gives larger permissible ratings.

(D) One Horsepower or Less, Nonautomatically Started. If not permanently installed then if it is within sight of the controller location, the ground-fault protection and branch-circuit short-circuit protection is sufficient. The sizings noted in Part IV are to be used. It can be on a 120-V circuit rated 20 A or less. If not within sight of the controller or permanently installed, it must comply with Section 430.32(B). If permanently installed comply with 430.32(B).

(E) Wound Rotor Secondaries. These can be protected by the motor-overload device.

430.33

Intermittent and Similar Duty

You can omit the separate overload protection for these types of motors and use only the branch-circuit, short-circuit and ground- fault protective device.

430.35

Shunting during Starting Period

There are cases where the overload protection can be shunted during starting.

430.36

FusesIn Which Conductor

When used as overload protection, put one in each ungrounded conductor and also the grounded conductor if the supply is three-phase, three-wire ac with one phase grounded.

430.37

Devices Other than FusesIn Which Conductor

Table 430.37 gives the requirements.

430.38

Number of Conductors Opened by Overload Devices

The number of conductors to be opened must prevent current to the motor for devices other than fuses or thermal protection.

430.39

Motor Controller as Overload Protection

This is permitted if it is in accordance with Table 430.37 and operator in the running position and also in the starting position for an ac motor.

If the device used for motor overload protection cannot clear short circuits, they must be protected by either fuses or circuit breakers or a motor short-circuit protector sized as noted in Section 430.52. There is one exception to the sizing rulegroup installations and where an overload relay is used.

430.42

Motors on General-Purpose Branch Circuits

This section indicates what overload protection must be used when motors are connected to general-purpose branch circuits. It must also comply with Article 210.

(A) Not over 1 Horsepower. Can be connected without overload protection if the rules of Section 430.32(B) and (D) and Section 430.53(A)(1) and (A)(2) are followed.

(B) Over 1 Horsepower. Each motor must have overload protection as noted in Section 430.32.

(C) Cord- and Plug-Connected. If no overload protection is provided, as in (a) above, the ratings of the plug and receptacle cannot be larger than 15 A 125 V or 10 A 250 V. If protection is required as in (b) above, the overload device must be part of the motor or appliance.

(D) Time Delay. Time delay must be provided in the branch-circuit and ground-fault devices to let the motor start.

430.43

Automatic Restarting

430.44

Orderly Shutdown

If an orderly shutdown is necessary to protect people rather than a quick opening of the circuit, the overload device can be connected to an alarm rather than open the circuit under the provisions of this section.

IV. Motor Branch-Circuit, Short-Circuit, and Ground-Fault Protection

430.51

General

430.52

Rating or Setting for Individual Motor Circuit

The device must carry the starting current. Table 430.152 lists the maximum settings of the protective devices. If the values in the tables are not a standard-size device, the rating can be increased to the next highest rating. If the rating in the table will not permit the motor to start, the rating can be increased as follows:

1. Nontime-delay fuse less than 601 A up to 400% of full-load current

2. Time-delay fuses up to 225% of full-load current

3. Circuit breakers (inverse time) up to 400% for full-load currents of up to 100 A and 300% for larger currents

4. Fuses between 601 and 6000 A up to 300% of full-load current

Also listed in this section are the rules for when instantaneous trip circuit breakers and motor short-circuit protectors can be used; rules for multispeed motors; multispeed motor; power electronic devices; rules for torque motors; and rules for phase converters. Where a maximum rating is indicated by the manufacturer, it cannot be exceeded. The reader is referred to this section of the Code for complete information.

430.53

Several Motors or Loads on One Branch Circuit

This section indicates under what conditions two or more motors or combined loads are permitted on one branch circuit.

(A) If none of the motors is greater than 1 hp, the circuit is protected at 20 A at 120 V or not more than 15 A at 600 V, the full-load current of each motor is not more than 6 A, individual overload protection meets the requirements of Section 430.32, and the rating marked on any controller for branch-circuit short circuit and ground-fault protection is not exceeded, more than one motor or combination loads are permitted on one branch circuit.

(B) When the branch-circuit short-circuit and ground-fault protective devices rating is not larger than required for the smallest motor and all motors have individual overload protection and the combination load will operate under these conditions, more than one motor or combination loads are permitted.

(C) Group installations of more than one motor or combination loads are permitted on one branch circuit if the overload devices and motor controllers are in a listed factory assembly, and motor short circuit and ground-fault protection are in the assembly or noted on the assembly; or if the controllers, overload devices, branch circuit, short circuit, and ground-fault devices are field-installed separately with manufacturer's instructions for use with each other and the following conditions are met:

1. The overload device must be approved for group installation and have a specified maximum fuse or inverse time circuit breaker rating, or both.

2. The motor controller for each motor must comply with the same rules as in (1) above.

3. The circuit breakers must be listed and have inverse time characteristics.

4. The rating of the fuse or circuit breaker for the branch circuit must comply with rules of Sections 430.52 and 240.3(B). It must be at least that of Section 430.52 for the largest motor and the sum of full-load ratings of other motors and loads.

5. The rating allowed in Section 430.40 for the smallest motor will also be the maximum for the branch-circuit fuses or inverse time circuit breakers.

6. For loads other than motor loads, the overcurrent protection complies with Parts I through VII of Article 240.

(D) In a group installation as described in (c) above, if the conductors to any single motor are not larger than the branch-circuit conductors or are not less than one-third the rating of the branch-circuit conductors in accordance with Section 430.22, and not farther than 7.5 m (25 ft.) from the controller and physically protected, then installation will not require individual branch-circuit short-circuit and ground-fault protection.

430.54

Multimotor and Combination-Load Equipment

The branch-circuit short-circuit and ground-fault device rating must not be larger than the rating marked on the equipment and comply with Section 430.7(D).

430.55

Combined Overcurrent Protection

As long as the rating is not larger than that required for overload protection in Section 430.32, the branch-circuit short-circuit and ground-fault protection and overload protection can be in one device.

430.56

Branch-Circuit Protective DevicesIn Which Conductor

430.57

Size of Fuseholder

430.58

Rating of Circuit Breaker

V. Motor Feeder Short-Circuit and Ground-Fault Protection

430.61

General

430.62

Rating or SettingMotor Load

The rating must be that of the largest branch-circuit protective device plus the full-load currents of all other motors. If larger feeders have been installed for future expansion, the rating can be that of the feeder. Reference is made to Sections 430.52 and 440.22(A). There are two exceptions and additional requirements.

430.63

Rating or SettingPower and Lighting Loads

When combined loads are installed in one feeder, the rating can be sufficient to carry the lighting and appliance load plus that permitted by Section 430.52 for a single motor and Section 430.62 for more than one motor and 440.22 for a single hermetic refrigerant motor-compressor. There is an excpetion for a motor control center.

VI. Motor Control Circuits

This part applies to particular conditions and contains modifications of general requirements of motor control circuits.

430.72

Overcurrent Protection

If the circuit is tapped from the load side of a branch-circuit protective device, it must have protection as specified in Section 430.72. If not, it must be protected as specified in Section 725.23. There are two exceptions to this rule.

There are also requirements for a control circuit transformer and additional requirements for conductor protection.

430.73

Mechanical Protection of Conductor

430.74

Disconnection

Motor control circuits must have a disconnecting means. One device can disconnect both the motor and control circuits from power, or separate ones can be used. If a transformer is used to reduce the voltage for the control circuit and it is located in the controller enclosure, the disconnecting means must be in the supply side of the transformer. There are a number of exceptions.

VII. Motor Controllers

The intention of this part is to require suitable controllers for all motors. When the motor is stationary and of not more than 1/8 hp, the branch-circuit protective device can be used if the motor is normally left running and cannot be damaged by not starting or by overloads. The plug and receptacle can be the controller if the motor is portable and not more than 1/3 hp.

430.82

Controller Design

430.83

Ratings

Generally, it must have a horsepower rating at least equal to that of the motor. There are a number of additional rules.

430.84

Need Not Open All Conductors

Unless it serves as a disconnecting device, it does not have to open all conductors.

430.85

In Grounded Conductors

This is permitted if it also simultaneously opens all other conductors.

430.87

Number of Motors Served by Each Controller

Each motor must normally have its own controller. There are exceptions to this rule if the motors are rated at not more than 600 V and the single controller is rated at not less than the sum of all motors it will control. Under these conditions it is allowed if more than one motor is used in one device or one overcurrent device is used for a group of motors [Section 430.53(A)] or the motors are in one room in sight of the controller.

430.88

Adjustable-Speed Motors

430.89

Speed Limitation

430.90

Combination Fuseholder and Switch as Controller

430.91

Motor Controller Enclosure Types

VIII. Motor Control Centers

A motor control center is an assembly of enclosed sections which principally contain motor control units and have a common power bus.

430.94

Overcurrent Protection

They must have overcurrent protection, either an overcurrent device upstream or a main device in the motor control center. It must be in accordance with Parts A, B and I of Article 240 and sized in accordance with the common power bus.

430.95

Service-Entrance Equipment

430.96

Grounding

All sections must be bonded with an equipment grounding conductor or grounding bus in accordance with Table 250.95. All equipment grounding conductors must terminate here. In the case of a single section a grounding termination point must be provided.

430.97

Busbars and Conductors

(A) Support and Arrangement. They must be protected from damage and held firmly. Only the conductors connected or used for control are allowed in a section.

(B) Phase Arrangement. Three phase buses are arranged A, B, C, left to right, top to bottom, or front to back when standing in the front.

(C) Minimum Wire Bending Space. As noted in Article 373.

(D) Spacings. As noted in Table 430.97.

(E) Barriers. Used in service-entrance motor control centers.

IX. Disconnecting Means

430.101

General

430.102

Location

It must be provided for and in sight from the controller location. An exception is made for motors over 600 V if it can be locked out and a warning sign is posted. Also, one disconnect can be used for a group of controllers for a multimotor device. A disconnecting means must also be located within sight of the motor location except in accordance with Section 430.102(a). There are some additional exceptions.

430.103

Operation

430.104

To Be Indicating

430.105

Grounded Conductors

If all conductors are opened simultaneously, one pole can be in a grounded conductor.

430.107

Readily Accessible

430.108

Every Disconnecting Means

430.109

Type

The disconnecting device must be noted in (A) below unless permitted in (B) through (G) meeting the specified conditions.

(A) General. It must be a horsepower-rated motor circuit switch. It can also be a molded case circuit breaker, molded case switch, an instantaneous trip circuit breaker which is part of a combination motor controller, a self-protected combination controller, or a manual motor controller if it is marked as such, if it is installed between the motor and the final motor branch circuit and ground-fault protective device, all of the items being listed. There are additional requirements for a manual motor controller. System isolation equipment must be listed for disconnection purposes and must be installed on the load side of the overcurrent protection and its disconnecting means. The disconnecting means must be one of those noted in 430.109(A)(1) through (A)(3).

(B) Stationary Motors of 1/8 Horsepower or Less. The branch circuit overcurrent device can be used.

(C) Stationary Motors of 2 Horsepower or Less. Stationary motors 2 hp or less and 300 V or less can have a general-use switch rated twice that of the motor. On ac circuits a general-use snap switch listed for ac use only can be used if the motor is not more than 80% of the rating of the switch. A listed manual motor controller can also be used if it is marked as being suitable as a motor disconnect and it is horsepower rated not less than the rating of the motor.

(D) Autotransformer-Type Controlled Motors. Motors over 2 hp up to 100 hp can use a general-use switch for motors with autotransformer controllers if the motor drives a generator with overload protection; the controller can interrupt locked rotor current, has no voltage release, and has running overload protection not larger than 125% of full-load current; separate fused or inverse time circuit breakers are provided and rated not more than 150% of full load current.

(E) Isolating Switches. Stationary motors more than 40 hp dc or 100 hp ac can have a general use or isolating switch if marked "Do Not Operate Under Load."

(F) Cord- and Plug-Connected Motors. A horsepower rated attachment plug and receptacle rated at least the rating of the motor can be used. This is not required for cord and plug appliances (Section 422.32), room air conditioners (Section 440.63) or a portable motor 1/3 hp or less.

(G) Torque Motors. A general-use switch can be used for a torque motor.

430.110

Ampere Rating and Interrupting Capacity

(A) The disconnecting means must have a rating of at least 115% of the full-load current rating of the motor. There is an exception.

(B) It must have a rating of at least 115% of the nameplate current for torque motors.

(C) For combination loads of motors or motors and other types of loads, the ratings of the disconnect must not be less than 115% of the total of the full-load current of all the loads. The Code makes reference to the method of determining the combined load.

430.111

Switch or Circuit Breaker as Both Controller and Disconnecting Means

A switch or circuit breaker can be used as the disconnect and controller if it complies with Section 430.83: if it opens all ungrounded conductors to the motor, has an overcurrent protective device which opens all ungrounded conductors to the switch, and is either an air-break switch, an inverse time circuit breaker, or an oil switch.

430.112

Motors Served by Single Disconnecting Means

Generally, a motor must have its own disconnecting means. There is an exception.

430.113

Energy from More than One Source

Generally, each source must have a disconnect. There are two exceptions.

X. Adjustable-Speed Drive Systems

430.120

General

430.122

ConductorsMinimum Size and Ampacity

430.124

Overload Protection

430.126

Motor Overtemperature Protection

430.128

Disconnecting Means

XI. Over 600 Volts, Nominal

430.221

General

430.222

Marking on Controllers

430.223

Conductor Enclosures Adjacent to Motors

430.224

Size of Conductors

430.225

Motor-Circuit Overcurrent Protection

430.226

Rating of Motor Control Apparatus

430.227

Disconnecting Means

XII. Protection of Live PartsAll Voltages

430.231

General

430.232

Where Required

If operating at 50 V or more, the exposed live parts must be guarded against accidental contact by enclosure or location. This can be done in a special room or enclosure, on a balcony or by installation at least 2.5 m (8 ft.) above the floor. There is an exception.

430.233

Guards for Attendants

If the only guards are by location, as noted in Section 430.132, then insulating mats or platforms are required.

XIII. GroundingAll Voltages

430.241

General

430.242

Stationary Motors

The frames must be grounded if in a wet location and not isolated, supplied by wire in a metal enclosure, in a hazardous location, or if motor operates over 150 V to ground.

430.243

Portable Motors

430.244

Controllers

430.245

Method of Grounding

XIV. Tables


Page 2

I. General

This section states the scope.

440.2

Definitions

440.3

Other Articles

Many additional articles are listed, such as 422, 424, 430, 460, and 470, and some not in Chapter 4.

440.4

Marking on Hermetic Refrigerant Motor-Compressors and Equipment

440.5

Marking on Controllers

440.6

Ampacity and Rating

The rating on the nameplate is to be used for a hermetic refrigerant motor compressor. There are two exceptions. Conductors are to be chosen from Tables 310.16 through 310.19 or in accordance with Section 310.15. Requirements are noted for multimotor equipment.

440.7

Highest Rated (Largest) Motor

440.8

Single Machine

A refrigerating system or air-conditioning system can be considered in accordance with Section 430.87, Exception, and Section 430.112, Exception.

II. Disconnecting Means

440.11

General

440.12

Rating and Interrupting Capacity

For hermetic refrigerant motor-compressor it must be at least 115% of the larger of the rated load or branch-circuit election circuit. There is an exception. If the rated load or locked rotor current comes out to be 100 hp or larger, use the provisions of Section 430.109(E). Information is given concerning equivalent horsepower and locked rotor current. Additional information is given concerning combination loads, horsepower rating, full load equivalent, small motor compressors and disconnecting means.

440.13

Cord-Connected Equipment

The separable connector or plug and receptacle can be used as the disconnecting means.

It must be within sight and readily accessible to the equipment. There are two exceptions.

III. Branch-Circuit Short-Circuit and Ground-Fault Protection

440.21

General

440.22

Application and Selection

(A) Rating or Setting for Individual Motor-Compressor. It must allow the motor to start. The NEC® therefore permits a rating or setting of up to 175% of the larger of the motor load or branch-circuit selection current. This can be increased to 225% if necessary. A 15-A rating is the least that can be required for branch-circuit, short-circuit and ground-fault protection.

(B) Rating or Setting for Equipment. It must also allow the equipment to start. If only one hermetic refrigerant motor compressor is used, conform to Section 422(A). If more than one hermetic refrigerant motor compressor is used, conform to Section 430.53 and the following:

(1) If the hermetic refrigerant motor compressor is the largest load, use Section 440.22(A) for this plus the other loads.

(2) If the hermetic refrigerant motor compressor is not the largest load, the sum is that of the rating of the motor compressor loads plus the value noted in Section 430.53(C)(4) or Section 240.3 for other loads, whichever is applicable. There are two exceptions. For a detailed analysis, refer to the NEC® and one of the many reference guides.

(C) If a maximum rating is indicated by the manufacturer, it should not be exceeded.

IV. Branch-Circuit Conductors

440.31

General

440.32

Single Motor-Compressor

The rating cannot be less than 125% of the largest of the motor compressor rated load or branch-circuit selection current. There is additional information concerning wye-start, delta-run motor compressor.

440.33

Motor-Compressor(s) with or without Additional Motor Loads

The ampacity must be the sum of the larger of the rated load or branch-circuit selection currents of all the motor-compressor loads plus full-load currents of the other motors plus 25% of the largest motor. There are two exceptions to this: one is for room air conditioners as per Part VII and the other is for interlocked motors.

The capacity must be adequate for all other loads, plus the motor-compressor load as specified in Sections 430.32 and 440.33. An exception is also made for interlocked circuitry.

440.35

Multimotor and Combination-Load Equipment

It cannot be less than that marked on the equipment as per Section 440.4(B).

V. Controller for Motor-Compressors

Generally, use the nameplate ratings. If more than one load is served, use the combined load rating [refer to Section 440.12(B)]. There are additional requirements.

VI. Motor Compressor and Branch-Circuit Overload Protection

440.51

General

440.52

Application and Selection

(A) Protection of Motor-Compressor. The following methods can be used: (1) an overload relay that will trip at not more than 140% of motor full-load current; (2) a thermal protector integral with the motor compressor; (3) a fuse or inverse time circuit breaker responsive to motor current and rated not more than 125% of motor current; and (4) a protective system furnished with the unit or specified for the unit.

(B) Protection of Motor-Compressor Control Apparatus and Branch-Circuit Conductors. It can be the same device protecting the motor-compressor in accordance with Section 440.52(A). There is an exception.

440.53

Overload Relays

440.54

Motor-Compressors and Equipment on 15- or 20-Ampere Branch CircuitsNot Cord and Attachment Plug-Connected

440.55

Cord and Attachment Plug-Connected Motor-Compressors and Equipment on 15- or 20-Ampere Branch Circuits

VII. Provisions for Room Air Conditioners

440.60

General

440.61

Grounding

440.62

Branch-Circuit Requirements

The branch circuit can have a load of only 80% of its rating for a cord- and plug-connected air-conditioning unit, if no other loads are on the circuit. If other loads are on the circuit, then the load of the cord- and plug-connected air-conditioning unit cannot be more than 50% of the rating of the branch circuit.

440.63

Disconnecting Means

The attachment plug can be used for a single-phase unit at 250 Volts or less if the manual control on the unit is readily accessible and within 1.8 m (6 ft.) of the floor or if a manual disconnecting means is readily accessible within sight of the unit.

The length of the cord cannot be larger than 3 m (10 ft.) for 120 V or 1.8 m (6 ft.) for 208 to 240 V.

440.65

Leakage Current Detection and Interruption (LCDI) and Arc Fault Circuit Interrupter (AFCI)

The following article titles are listed for reference: Article 445Generators; Article 450Transformers and Transformer Vaults (Including Secondary Ties); Article 455Phase Converters; Article 460Capacitors; Article 470Resistors and Reactors; Article 480Storage Batteries; Article 490Equipment, over 600 Volts, Nominal.


Page 3

500.1

ScopeArticles 500 through 504

Articles 500 through 504 describe the electrical and electronic equipment and wiring requirements in hazardous (classified) locations where a fire or explosion hazard can exist because of flammable gases or vapors, flammable liquids, combustible dust, or ignitible fibers or flyings. There are fine print notes.

500.2

Definitions

500.3

Other Articles

All applicable sections of this Code apply unless they are modified by Articles 500 through 504.

(A) Documentation. All areas that are classified must have the proper documentation. This documentation must be available.

Note: Space does not permit a complete description of this chapter. This is true of the entire NEC® but is again stated here. Only the highlights are noted. The reader should refer to the NEC® for complete descriptions.

(B) Reference Standards

500.5

Classification of Locations

(A) Classifications of Locations. The classifications are made by the properties of the items in the room under the listings in this chapter.

(B) Class I Locations. Areas where flammable gases or vapors are in the air in quantities that can cause explosive or ignitible mixtures are classified as Class I. They are further broken down into two divisions:

(1) Class I, Division 1. This is where ignitible concentrations of gases or vapors can exist normally; where they may exist because of maintenance or leakage; or where they might exist because of breakdowns or faulty operations.

(2) Class I, Division 2. This is where volatile flammable liquids or flammable gases are used but are normally in closed containers or systems and can escape only as a result of a breakdown or rupture; where ignitible concentration of gases or vapors normally cannot occur because of mechanical ventilation; where an area is next to a Class I, Division 1, location and some leakage between areas occurs.

(C) Class II Locations. These are hazardous because of combustible dust. They are also broken down into two divisions.

(1) Class II, Division 1. This is where combustible dust is in the air and can ignite under normal conditions due to its concentration, or where a breakdown of equipment can cause these concentrations and an ignitible source, or Group E combustible dust may be present in hazardous quantities.

(2) Class II, Division 2. This is where combustible dust is in quantities in the air to have explosive or ignitible mixtures due to abnormal operations; or the combustible dust is not in high enough quantities to interfere with the normal operations of electrical equipment or other apparatus but it could be suspended in the air if there were infrequent malfunctions of the equipment; or where the accumulations of the combustible dust in the vicinity of electrical equipment could become ignitible or interfere with the safe dissipation of heat from the electrical equipment as a result of abnormal operation of this equipment.

(D) Class III Locations. Areas that have ignitible fibers or flyings in a concentration not likely to cause ignition are classified as Class III. They are also further broken down into two divisions.

(1) Class III, Division 1. Areas where the fibers or flyings are handled, manufactured, or used.

(2) Class III, Division 2. Areas where the fibers or flyings are stored or handled other than in the process of manufacture.

This section indicates the groupings of various air mixtures. Requirements are given for approval for class and properties, marking, and temperature.

500.7

Protection Techniques

This paragraph describes various protection techniques which are acceptable for electrical and electronic equipment in hazardous (classified) locations.

This paragraph describes the equipment construction and installation.

500.9 Specific Occupancies

These are covered in Articles 510 through 517 and include garages, aircraft hangars, gasoline dispensing and service stations, bulk storage plants, spray application, dipping and coating processes, and health care facilities.


Page 4

I. General

501.1

Scope

501.5

General

This article refers to those areas classified as Class I in Section 500.5.

II. Wiring

(A) Class I, Division 1. Only threaded rigid metal conduit, threaded steel intermediate conduit, or Type MI cable can be used. Boxes and fittings must be approved for Class I, Division 1. At least five threads must be engaged. MI cable has to be installed to prevent stress at the terminations. There is one exception. There are also requirements for industrial establishments with the use of MC-HC and ITC-HC cable.

(B) Class I, Division 2. Methods permitted are threaded rigid metal conduit; threaded steel intermediate metal conduit; enclosed gasketed busways; enclosed gasketed wire-ways; Type MI, MC, MV, or TC cable with approved terminations; Type PLTC cable; type ITC cable as permitted in 727.4 and all methods permitted in 501.10(A). Explosion-proof boxes or fittings are not required. Additional requirements and exceptions are noted.

501.15

Sealing and Drainage

Seals must be provided and approved items must be used.

(A) Conduit Seals, Class I, Division 1

  1. A seal must be placed in each conduit run which enters the enclosure for a switch, circuit breaker, relay, resistor, fuse, or any item that can cause arcing, sparking, or high temperatures or the entry is metric designator 53 (trade size 2) or larger and the enclosure contains terminals, splices, or taps. The seal must be within 450 mm (18 in.) of the enclosure. There is a listing of the enclosures or fittings that are allowed between the seal fitting and enclosure. The conduit bodies cannot be larger than the largest trade size of the conduits.
  2. If the enclosure is pressurized and the conduit is not, the seals must be installed within 450 mm (18 in.) of the pressurized enclosure.
  3. If a run of conduit between two enclosures is not more than 914 mm (36 in.), one seal not more than 450 mm (18 in.) from an enclosure is acceptable.
  4. A seal is required where a conduit run leaves a Class I, Division 1 location. The sealing fitting be within 3.05 m (10 ft.) of the boundary on either side. The conduit must not have a fitting, union, coupling, or box between the seal and point of leaving the Class I, Division 1 location. There are exceptions.

(B) Conduit Seals, Class I, Division 2

  1. Seals are required for connection to explosion-proof enclosures and must comply with 501.15(A)(1) through (A)(3) above.
  2. A seal is required when the conduit run leaves this area to an unclassified area. This paragraph describes additional requirements. There are four exceptions.

(C) Class I, Divisions 1 and 2. These are general rules.

  1. The fittings must be listed for the location used.
  2. The compound must provide a proper seal.
  3. The thickness of the compound must be at least the trade size of the conduit and not less than 16 mm (5/8 in.).
  4. Splices and taps cannot be made in fittings that are used for sealing.
  5. Assemblies must be identified for the locations.
  6. Conductor cross-sectional area in a seal cannot be more than 25% of a conduit of the same size unless identified for a higher fill.

(D) Cable Seals, Class I, Division 1

(E) Cable Seals, Class I, Division 2

(F) Drainage. In certain cases drainage of accumulated liquid is permitted and even required. Special requirements must be followed.

501.20

Conductor Insulation, Class I, Divisions 1 and 2

If the conductors come in contact with condensed vapors or liquids, the insulation must be identified for this use or have protection provided by a lead sheath or another approved sheath.

501.25

Uninsulated Exposed Parts, Class I, Divisions 1 and 2

There can be no uninsulated exposed parts such as conductors, buses, etc., that operate at more than 30 volts. This limit is reduced to 15 volts in wet locations. The protection must be in accordance with 500.7(E), 500.7(F), or 500.7(G).

501.30

Grounding and Bonding, Class I, Divisions 1 and 2

Wiring and equipment must be grounded in accordance with Article 250. Bonding jumpers with proper fitting or other approved means of bonding must be used. Locknut bushings and double locknut types of contacts are not acceptable. The means of bonding applies to all raceways, fittings, boxes, enclosures, etc., between Class I locations and the grounding point for service equipment or separately derived systems. If flexible conduit is used it must have internal or external bonding jumpers in parallel with each conduit. It must also comply with the requirements of Section 250.120 where flexible metal or liquidtight flexible metal conduit is used. There are exceptions.

501.35

Surge Protection

501.40

Multiwire Branch Circuits

III. Equipment

501.100

Transformers and Capacitors

(A) Class I, Division 1

  1. Containing liquid that will burn. They must be installed in a vault complying with Sections 450.41 through 450.48 with no door or opening to the Class I, Division 1 locations, with proper ventilation and the vents going outside the buildings and being large enough to relieve an explosion. The ducts for the vents must be constructed of reinforced concrete.
  2. Not containing liquid that will burn. These must be installed in a vault as noted in (a)(1) or be approved for a Class I location.

(B) Class I, Division 2. In these locations they must be in accordance with Sections 450.21 through 450.27.

501.105

Meters, Instruments, and Relays

(A) Class I, Division 1. They must be in Class I, Division 1 enclosures.

(B) Class I, Division 2

  1. Contacts. Make-or-break contacts, switches, circuit breakers, etc., must have identified Class I, Division 1, enclosure in accordance with 501.105(A). Four exceptions are: immersed in oil, in a hermetically sealed chamber, in nonincendive circuits, and where part of a listed nonincendive component.
  2. Resistors and similar equipment. These must comply with Section 501.105(A). An exception is made if the exposed surface does not exceed 80% of the ignition temperature and there are no make-or-break or sliding contacts. The exception does not apply to thermionic tubes.
  3. Without make-or-break contacts. General-purpose enclosures can be used for this category for transformer windings, impedence coils, solenoids, and other windings.
  4. General-purpose assemblies. If an assembly has items that can use general-purpose enclosures [noted in 501.105(B)(1), (B)(2), and (B)(3)], a single, general-purpose enclosure can be used. If equipment noted in 501.105(B)(2) is used, the maximum surface temperature must be noted.
  5. Fuses. Fuses for instrument circuits not subject to overloading can be mounted in general-purpose enclosures if approved in 501.105(B)(1) through (B)(4), and if they are preceded by a switch in accordance with 501.105(B)(1).
  6. Connections. Process control can use a cord, plug, and receptacle if (a) a switch is complying with 501.105(B)(1) is used so that the plug is not depended upon to interrupt current; (b) current is not greater than 3 A at 120 V; (c) cord is not longer than 900 mm (3 ft.), is rated for extra hard usage or hard usage depending on location, and uses locking and grounding-type plug and receptacle; only necessary receptacles are provided; and (e) a warning is posted against unplugging under load.

501.115

Switches, Circuit Breakers, Motor Controllers, and Fuses

(A) Class I, Division 1. Must be in an enclosure and the entire assembly must be identified for Class I locations.

(B) Class I, Division 2

  1. Must be in enclosures identified for Class I, Division 1, locations unless a general-purpose enclosure is used and it is hermetically sealed, or has oil-immersed make-or-break contacts with special requirements, the device is solid state without contacts, or current interruption occurs in a factory-sealed explosion-proof chamber approved for the location.
  2. If not intended to interrupt current, a general-purpose enclosure can be used with a disconnecting or isolating switch for transformers or capacitor banks.
  3. Standard plug or cartridge fuses can be used in certain cases, but they must have enclosures identified for the location. If they are oil immersed, they can be placed in general-purpose enclosures.
  4. Within luminaires (lighting fixtures), listed cartridge fuses are permitted as supplementary protection.

501.120

Control Transformers and Resistors

Transformers, impedance coils, and resistors are covered by this section.

(A) Class I, Division 1. In this location they must have enclosures identified for Class I, Division 1.

(B) Class I, Division 2. In this location switching mechanisms must be in accordance with Section 501.6(B). General-purpose enclosures can be used for coils and windings. Resistors must have enclosures identified for Class I locations. If the resistor is fixed and the maximum operating temperature is not more than 80% of the ignition temperature of the gas or vapor, a general-purpose enclosure can be used.

501.125

Motors and Generators

(A) Class I, Division 1. In this location they must be either identified for Class I, Division 1 locations or be totally enclosed with a positive pressure ventilation (the arrangement being that the device cannot start until the ventilation has started and 10 volumes of air have been purged from the enclosure) or be totally enclosed filled with inert gas. There is also a requirement for the type submerged in a liquid.

(B) Class I, Division 2. In this location you can have open or nonexplosion-proof enclosed motors if they do not have brushes, switching mechanisms, or arc-producing devices. If they do have brushes, switching mechanisms, or arc-producing devices, the motor or generator must be identified for Class I, Division 1, locations or the devices must be in Class I, Division 1 identified enclosures as per Section 501.105(B). A requirement is noted for the surface temperature of space heaters used to prevent condensation. There are other specific requirements.

501.130

Luminaires (Lighting Fixtures)

(A) Class I, Division 1. The entire fixture assembly must be identified for a Class I, Division 1 location and be protected against physical damage. Pendant luminaires (fixtures) must be wired and hung through rigid metal conduit or threaded steel intermediate conduit. Stems longer than 300 mm (12 in.) must have additional lateral bracing not more than 300 mm (12 in.) from the end of the stem or a flexible fitting approved for a Class I, Division 1 location. All boxes, fittings, etc., must be identified for Class I, Division 1 locations.

(B) Class I, Division 2. Portable lighting equipment must comply with Class I, Division 1 requirements. There is an exception when it is mounted on a moveable stand and connected by flexible cord. Fixed lighting must be protected against physical damage. If there is danger of falling sparks or hot metal igniting vapors or gases, proper enclosures must be provided. If the operating temperature will exceed 80% of the ignition temperature of the gases or vapors, they must comply with Section 501.130(A)(1) or be of the type that has been tested to determine the temperature range or operating temperature marked. Pendant luminaires (fixtures) have the same rules as Class I, Division 1 locations. Switches must be in accordance with Section 501.6(B)(1). Starting equipment for electric-discharge lamps must be in accordance with Section 501.7(B) unless it is part of a "thermally protected fluorescent lamp ballast" and the lighting fixture has been identified for this location.

501.135

Utilization Equipment

501.140

Flexible Cords, Class I, Divisions 1 and 2

These are permitted only to connect the portable equipment to the fixed part of the system. They can also be used under certain conditions where a greater degree of movement is needed. As such, they must be identified for extra hard usage, contain a grounding conductor, be connected to the supply conductors or terminals in an approved way, ensure that there is no tension applied, and be provided with seals where necessary. Exceptions are made in Sections 501.10(B) and 501.105(B)(6). There is additional information concerning electrical submersible pumps and electric mixers.

501.145

Receptacles and Attachment Plugs, Class I, Divisions 1 and 2

Must be of the grounding type and approved for Class I locations except as provided in Section 501.105(B)(6).

501.150

Signaling, Alarm, Remote-Control, and Communication Systems


Page 5

I. General

502.1

Scope

502.5

General

This article refers to areas classified as Class II. Explosion-proof equipment cannot be required and used unless identified for Class II locations.

II. Wiring

(A) Class II, Division 1. Only threaded rigid metal conduit, threaded steel intermediate metal conduit, Type MI cable can be used. Boxes and fittings can have no openings and have threaded bosses so that no dust can come in. If used where the dust is combustible electrically conductive, they must be approved for Class II locations. If a flexible connection must be used, it has to be either a dust-tight flexible connector, liquidtight flexible metal conduit, liquidtight non-metallic conduit, certain types of interlocked armor type MC cable with certain requirements, or a flexible cord for extra-hard usage and bushed fittings. The flexible cord must comply with section 502.140. There is an exception for certain industrial establishments.

(B) Class II, Division 2. Methods permitted are rigid metal conduit, intermediate metal conduit, electrical metal tubing, dust-tight wireways, or Type MI or MC cable that have listed termination fittings or Type PLTC, MC, ITC, or TC cable, all under certain conditions. There is an exception. Also, wireways, fittings, and boxes must be dust tight. The requirements for flexible connections are noted in 502.10(A)(2). There are additional requirements.

502.15

Sealing, Class II, Divisions 1 and 2

If a raceway connects two enclosures, one being dust-ignition-proof, the other not, provision must be made to prevent dust from getting into the dust-ignition-proof enclosures. This can be done with seals, a minimum of 3.05 m (10 ft.) of horizontal raceway, or a minimum of 1.5 m (5 ft.) of vertical raceway or a raceway extending only horizontally and downward from the dust-ignition proof enclosure and complying with the above requirements for horizontal or vertical raceways. If the dust-ignition-proof enclosure is connected to one in an unclassified area, a seal is not required.

502.25

Uninsulated Exposed Parts, Class II, Divisions 1 and 2

There can be no uninsulated exposed parts such as conductors, buses, etc., that operate at more than 30 volts. This limit is reduced to 15 volts in wet locations. The protection must be in accordance with 500.7(E), 500.7(F), or 500.7(G).

502.30

Grounding and Bonding, Class II, Divisions 1 and 2

Ground, in accordance with Article 250 and the requirements of 502.30(A) and (B), all wiring and equipment.

(A) Bonding jumpers with proper fittings or other approved means must be used. Locknut bushings and double lock-nut contacts alone are not to be depended on. The means of bonding applies to all raceways, fittings, boxes, enclosures, etc., between Class II locations and the grounding point for service equipment or separately derived systems. There is an exception.

(B) If flexible conduit is used, it must have internal or external bonding jumpers in parallel with each conduit. It must also comply with the requirements of Section 250.102. There is an exception.

502.35

Surge Protection, Class II, Divisions 1 and 2

502.40

Multiwire Branch Circuits

III. Equipment

502.100

Transformers and Capacitors

(A) Class II, Division 1

  1. Containing liquid that will burn. They must be installed in vaults complying with Section 450.41 through 450.48 outside the Division I location with self-closing fire doors, and have proper ventilation and pressure relief.
  2. Not containing liquid that will burn. They must be installed in a vault as per Sections 450.41 through 450.48 or have the entire assembly identified for a Class II location.
  3. If the area has a metal dust such as magnesium, aluminum, etc., you cannot install a transformer or capacitor.

(B) Class II, Division 2

  1. Containing liquid that will burn. Must be installed in vaults as per Sections 450.41 through 450.48.
  2. Containing Askarel. If it is larger than 25 kVA, it must have a pressure relief vent, have a way of absorbing gases from inside, and have an air space of at least 150 mm (6 in.) between the case and any combustible material.
  3. Dry-type transformers. Must be in vaults or not operate over 600 V, with the windings and terminals enclosed without ventilating or other openings.

502.115

Switches, Circuit Breakers, Motor Controllers, and Fuses

(A) Class II, Division 1. Their enclosures must be dust-ignition-proof. If the dust is a hazardous metal (magnesium, etc.), the enclosure must be identified for this specific type of location. If disconnecting and isolating switches are not installed where there is electrically conductive dust, are not to interrupt current, and have no fuses, the enclosure only has to be tight so as to keep the entrance of dust to a minimum and have no openings, as well as have close-fitting or telescoping covers.

(B) Class II, Division 2. The enclosures only have to be dust-tight.

502.120

Control Transformers and Resistors

(A) Class II, Division 1. The enclosures must be dust-ignition-proof identified for a Class II location. If they are installed in a location with hazardous metal dust (magnesium, etc.), the enclosure must be identified for this specific type of location.

(B) Class II, Division 2. In these locations, the switching mechanisms must have a dust-tight enclosure. If they are in the same location as the switching mechanism, they must have tight metal enclosures with no openings. Resistors must have identified Class II enclosures unless their temperature is not higher than 248°F and they are either nonadjustable or part of an automatic timing system. In that case the enclosures have only to be tight with no openings. There are other requirements.

502.125

Motors and Generators

(A) Class II, Division 1. They must be either totally enclosed pipe-ventilated and meet the temperature restrictions of Section 502.5 or be identified for locations classified as Class II, Division 1.

(B) Class II, Division 2. They must be either totally enclosed pipe-ventilated, totally enclosed fan-cooled, totally enclosed waterair-cooled, totally enclosed nonventilated or dust-ignition-proof with full load external temperature in accordance with Section 500.8(C)(2). There are exceptions for these types of motors if the authority having jurisdiction feels that the machines are easily cleaned and maintained and there will not be a large accumulation of dust.

502.128

Ventilating Piping

The piping must (1) be metal at least 0.53 mm (0.021 in.) thick or of noncombustible material of equal substance, (2) be screened at the outside ends, (3) lead to the outside of the building and have clean air available, and (4) be protected against corrosion and physical damage. In addition, it must comply with:

(A) Class II, Division 1. The pipes must be entirely dust-tight. They must also be either riveted and soldered, bolted and soldered, welded, or be dust-tight by another effective means.

(B) Class II, Division 2. The pipes must be tight enough to prevent the entrance of dust in appreciable quantities.

502.130

Luminaires (Lighting Fixtures)

(A) Class II, Division 1. The luminaires (fixtures) must be identified for Class II locations and additionally for hazardous metal dust if so located. They must be protected against physical damage. Pendant fixtures must be suspended using threaded rigid metal conduit, threaded steel intermediate metal conduit, or approved chains or other means. If the stem is longer than 300 mm (12 in.), it must be braced within 300 mm (12 in.) from the lower end or have a flexible fitting not more than 300 mm (12 in.) from the upper end. If conduit is not used for the wiring, the cord must be listed for hard usage and proper seals must be used. All boxes, fittings, etc., must be identified for Class II locations.

(B) Class II, Division 2. Portable lighting equipment must be identified for Class II locations. A fixed luminaire (lighting fixture) must only minimize the collection of dust and prevent the escape of sparks. It must also have maximum wattage permitted for temperatures in accordance with Section 500.8(C)(2). Luminaires (fixtures) in these locations must also be protected against physical damage. Requirements for pendant fixtures in Division 2 are basically the same as for Division 1. One difference is that seals are not required. The requirements of Section 502.120(B) apply here for starters and control equipment for electric-discharge lamps.

502.135

Utilization Equipment

(A) Class II, Division 1. Must be identified for Class II locations. If hazardous dust is present, it must also be identified for that location.

(B) Class II, Division 2. Heaters must be identified for Class II locations. There is one exception. Motors must be in accordance with Section 502.125(B). Dust-tight enclosures are required for circuit breakers, switches, and fuses. Section 502.120(B) is applied to transformers, impedance coils, and resistors.

502.140

Flexible Cords, Class II, Divisions 1 and 2

502.145

Receptacles and Attachment Plugs

(A) Class II, Division 1. Must be identified for Class II locations and have a grounding conductor connection.

(B) Class II, Division 2. Must also have a grounding conductor connection. They cannot permit the supply circuit to open with exposed live parts.

502.150

Signaling, Alarm, Remote-Control, and Communication Systems; Meters, Instruments, and Relays


Page 6

I. General

503.1

Scope

503.5

General

Maximum surface temperatures for equipment permitted under operating conditions are 165°C (329°F) for normal operation or 120°C (248°F) if the equipment can be overloaded.

II. Wiring

(A) Class III, Division 1. Use only rigid metal conduit, rigid nonmetallic conduit, intermediate metal conduit, electrical metallic tubing, dust-tight wireways or Type MI or MC cables with listed fittings. Fittings and boxes must be dust tight. Refer to this section for the requirements for flexible connections and nonincendive field wiring.

(B) Class III, Division 2. Same requirements as Division 1. An exception is made for storage areas with no machinery, where open wire on insulators can be used complying with Article 398, specifically Section 398.15(C).

503.25

Uninsulated Exposed Parts, Class III, Divisions 1 and 2

There can be no uninsulated exposed parts such as conductors, buses, etc., that operate at more than 30 volts. This limit is reduced to 15 volts in wet locations. The protection must be in accordance with 500.7(E), 500.7(F), or 500.7(G). There is an exception as provided in 503.155.

503.30

Grounding and Bonding, Class III, Divisions 1 and 2

As per Article 250. Also, the same requirements hold true for bonding and grounding as in Sections 501.16, and 502.16. There are exceptions. Rules for equipment grounding conductors are noted.

III. Equipment

503.100

Transformers and Capacitors, Class II, Divisions 1 and 2

Must be in accordance with Section 502.100(B).

503.115

Switches, Circuit Breakers, Motor Controllers and Fuses, Class III, Divisions 1 and 2

These devices must have dust-tight metal enclosures.

503.120

Control Transformers and Resistors, Class III, Divisions 1 and 2

Must be in dust-tight enclosures complying with temperature limitations in Section 503.5.

503.125

Motors and Generators, Class III, Divisions 1 and 2

Must be totally enclosed pipe ventilated, totally enclosed non-ventilated, or totally enclosed fan cooled. There is an exception where the authority having jurisdiction will permit it.

503.128

Ventilating Piping, Class III, Divisions 1 and 2

Must be metal at least 533 mm (0.021 in.) thick or equal noncombustible material, have physical damage protection, go directly outside to clean air, and be screened. The pipes must be tight enough to prevent "appreciable quantities" of fibers or flyings from getting in and sparks getting out.

503.130

Luminaires (Lighting Fixtures), Class III, Divisions 1 and 2

Protect against physical damage. Prevent entrance of fibers or flyings or escape of sparks. Pendant stems must be threaded rigid metal conduit, threaded intermediate metal conduit, or threaded metal tubing. Chains with approved fittings can be used for suspending fixtures. The same rules apply for bracing stems over 3.5 mm (12 in.) long as Class II. Portable lamps must have handles, guards, and the lampholders have no switches, exposed parts, or receptacles.

503.135

Utilization Equipment, Class III, Divisions 1 and 2

Heaters: identified for Class III locations. Motors: Section 503.125. Switches, circuit breakers, motor controllers, and fuses: 503.115.

503.140

Flexible Cords, Class III, Divisions 1 and 2

They must be listed for extra-hard usage, have a grounding conductor, be connected in an approved manner, be supported so as to prevent tension on the connections, and have provisions to prevent fibers or flyings from entering the boxes or fittings.

503.145

Receptacles and Attachment Plugs, Class III, Divisions 1 and 2

They must be of the grounding type, and designed to prevent the escape of sparks or molten particles and minimize the entry of fibers or flyings. An exception is provided where permitted by the authority having jurisdiction.

503.150

Signaling, Alarm, Remote-Control, and Local Loud Speaker Intercommunication Systems, Class III, Divisions 1 and 2

503.155

Electric Cranes, Hoists, and Similar Equipment, Class III, Divisions 1 and 2

503.160

Storage-Battery Charging Equipment, Class III, Divisions 1 and 2


Page 7

Article 505 Class I, Zone 0, 1, and 2 Locations

If this article is used, the equipment selection, wiring methods, and area classification must be under the supervision of a qualified registered professional engineer.

505.2

Definitions

505.3

Other Articles

505.4

General

505.5

Classification of Locations

505.6

Material Groups

505.7

Special Precautions

505.8

Protection Techniques

505.9

Equipment

505.15

Wiring Methods

505.16

Sealing and Drainage

505.17

Flexible Cords, Class I, Zones 1 and 2

505.18

Conductors and Conductor Insulation

505.19

Uninsulated Exposed Parts

505.20

Equipment Requirements

505.21

Multiwire Branch Circuits

505.22

Increased Safety "e" Motors and Generators

505.25

Grounding and Bonding

Article 506 Zone 20, 21, and 22 Locations for Flammable Dusts, Fibers, and Flyings

506.1

Scope

506.2

Definitions

506.4

General

506.5

Classification of Locations

506.6

Special Precautions

506.8

Protection Techniques

506.9

Equipment Requirements

506.15

Wiring Methods

506.16

Sealing

506.17

Flexible Cords

506.20

Equipment Installation

506.21

Multiwire Branch Circuits

506.25

Grounding and Bonding

Article 510 Hazardous (Classified) LocationsSpecific

Articles 511 through 517 cover specific locations that might be hazardous. The following article titles are listed for reference: Article 511Commercial Garages, Repair and Storage; Article 513Aircraft Hangars; Article 514Motor Fuel Dispensing Facilities; Article 515Bulk Storage Plants; Article 516Spray Application, Dipping, and Coating Processes.

Article 517 Health Care Facilities

I. General

FPN: Rules that are followed by a reference in brackets contain text that has been extracted from NFPA-2002, Standard for Health Care Facilities. Only editorial changes were made to the extracted text to make it consistent with the NEC.

Electrical construction and installation criteria for health care facilities that provide service to human beings are covered in this article. Performance, maintenance, and testing criteria are covered in NFPA 99 and other appropriate health care documents. Veterinary facilities are not covered. The reader is referred to NFPA 99.

Parts II and III are intended to be applied to both single-function buildings and to applicable portions of multifunction buildings. The example used is a doctor's examining room in a residential custodial care facility having to comply with Section 517.10.

Many definitions are listed in this section that are not covered in Article 100. These are specific to health care facilities. The reader should refer to these in the Code.

II. Wiring Design and Protection

Generally, this part applies to all health care facilities. Part II does not apply to business offices, corridors, waiting rooms, and similar areas in clinics, medical and dental offices, and outpatient clinics, and if wired in accordance with Chapters 1, 2, 3, and 4 of the Code, patient sleeping areas in nursing homes and limited care facilities.

517.11

General Installation-Construction Criteria

It is important that the system installed maintain low potential differences between exposed conductive surfaces which are likely to become energized and the patient could contact.

All the requirements of Chapters 1 through 4 must be followed unless they are changed in this article.

517.13

Grounding of Receptacles and Fixed Electric Equipment in Patient Care Areas

(A) Wiring Methods. Branch circuits serving patient care areas must have a ground path for fault current by being installed in a metal raceway or cable having a metallic armor or sheath assembly which qualifies as an equipment grounding return path. This is in addition to all other requirements of this section.

(B) Insulated Equipment Grounding Conductor. If operated over 100 V, the grounding terminal of all receptacles and noncurrent-carrying areas of fixed equipment that a person can contact and may become energized must be grounded using an insulated copper conductor. It must be sized according to Table 250.122 and be installed in a metal raceway or as a part of listed cables that have metallic armor or sheath assembly with the branch-circuit conductors supplying the equipment or receptacle. There are two exceptions.

517.14

Panelboard Bonding

The equipment grounding busses of all panelboards serving the same patient vicinity must be bonded together. This is to be done using a continuous insulated copper conductor 10 AWG or larger. If two or more panelboards serve the same patient vicinity and are served from different transfer switches in the emergency system, then the equipment grounding terminal buses have to be bonded together with an insulated continuous copper conductor. The conductor cannot be smaller than 10 AWG.

517.16

Receptacles with Insulated Grounding Terminals

517.17

Ground-Fault Protection

(A) Applicability. Hospitals and other buildings that have or provide essential utilities or services for critical care areas or use life support equipment must comply with 517.17.

(B) Feeders. If ground-fault protection is used at the service disconnect as per Section 230.95 or 215.10, an additional step is needed at the next level of feeder away from the service. There are three areas listed where the additional level of ground- fault protection cannot be installed.

(C) Selectivity. The system must be fully selective. Six-cycle separation between the levels is required.

(D) Testing

517.18

General Care Areas

(A) Patient Bed Location. Each patient bed location must have at least two branch circuits, at least one of them must originate from the normal system and one from the emergency system. All branch circuits on the normal system must come from the same panel-board. There are three exceptions to this.

(B) Patient Bed Location Receptacles. Each location must have at least four receptacles, either single, duplex, or a combination. They must all be hospital grade and grounded with an insulated copper conductor in accordance with Table 250.122. There are two exceptions to this.

(C) Pediatric Locations. The receptacles must be listed tamper resistant or have a listed tamper resistant cover.

517.19

Critical Care Areas

(A) Patient Bed Location Branch Circuits. Each patient bed location must have at least two branch circuits, at least one from the normal system and one from the emergency system. One circuit on the emergency system that supplies no other bed location must be available at each bed location. All branch circuits from the normal system must come from one panelboard. The emergency receptacles must be identified and have the panelboard and circuit number of its supply noted. There are two exceptions.

(B) Patient Bed Location Receptacles. Each location must have at least six receptacles, either single, duplex, or a combination of both. At least one must be connected to the normal system or an emergency system supplied by a different transfer switch than the other receptacles in that location. They must all be hospital grade and grounded with an insulated copper conductor to the reference grounding point.

(C) Patient Vicinity Grounding and Bonding (Optional). A patient equipment grounding point is allowed in the patient vicinity. It can have grounding and bonding jacks listed for that purpose. All the grounding terminals on the receptacles must be connected to the patient equipment grounding point if supplied with an equipment bonding jumper no smaller than 10 AWG. This jumper can be looped or run centrically.

(D) Panelboard Grounding. Grounding of panelboards and switchboards must be accomplished if a grounded distribution system is used and metal feeder raceway or Type MC or MI cable is used. There are three acceptable means noted for use at each termination or junction point in the system.

(E) Additional Protective Techniques in Critical Care Areas (Optional). Isolated power systems are permitted.

(F) Isolated Power System Grounding

(G) Special-Purpose Receptacle Grounding

(A) In a wet location two methods can be used to protect personnel. Either a ground-fault circuit interrupter can be used if power interruption is acceptable or an isolated power supply can be used. There is an exception.

(B) Isolated power supplies must conform to Section 517.160.

517.21

Ground-Fault Circuit Protection for Personnel

Not required for receptacles in critical care areas that have the toilet and basin in the patient room.

III. Essential Electrical System

This system is needed to provide light and power for systems essential to life safety and orderly cessation of procedures during a power failure of the normal electrical supply. The types of structures and services are listed in the Code. The reader is also referred to NFPA 99-2002 for further information as to the need for an essential electrical system.

517.26

Application of Other Articles

517.30

Essential Electrical Systems for Hospitals

(A) Applicability

(B) General. The system is comprised of two separate systems, the emergency system and the equipment system. The emergency systems has a life safety branch and a critical branch. The equipment system supplies power to major equipment. The number of transfer switches depends on many design considerations. One switch can be used for a system with a maximum demand of 150 kVA (120 kw). Loads not noted in Article 517 must have their own transfer switch and must not transfer if it overloads the generator and must automatically shed if the generating equipment becomes overloaded. Continguous facilities can be served by the hospital power and alternate power sources. [NFPA99, 13.3.4.3]

(C) Wiring Requirements. The life safety and critical branch must be kept separate from all other wiring and equipment except for four conditions. The wiring of the emergency system must be mechanically protected. There are five methods accepted. When isolated power systems are used in anesthetizing locations or special environments, each must be supplied by a separate circuit.

(D) Capacity of Systems. The system must be able to supply the entire load. There is now a statement on demand calculations.

(E) Receptacle Identification. Must be distinctively marked. [NFPA99, 4.4.2.2.4.2(B)]

This is divided into two required branches, the life safety and the critical. This system must be automatically restored to power within 10 seconds of the loss of the normal supply. [NFPA99, 4.4.2.2.2.1, 4.4.3.1]

517.32

Life Safety Branch

The Code lists all the items that are required to be on the life safety branch. They are basically illumination of means of egress, exit signs, alarm and alerting systems, communication systems, generator set location, elevators, and automatic doors. The reader is referred to the Code for the exact list. No function other than those listed can be connected to the life safety branch.

The Code lists all the items that are required to be on the critical branch. They are basically task illumination and selected receptacles for the isolated power system, anesthetizing locations, patient care areas, additional specialized areas, nurse call systems, blood, bone and tissue bank, telephone equipment room and closets, special areas, and special circuits. The critical branch can be divided into two or more branches. The reader is referred to the Code for the exact list.

517.34

Equipment Source Connection to Alternate Power Source

This section describes what equipment must be placed on the equipment system. It also describes how the system is energized (i.e., automatic, delayed automatic, and manually). The reader is referred to the Code for the exact requirements.

(A) Two Independent Sources of Power. There must be a normal source of power and an alternate source of power for use when the normal source is interrupted. [NFPA99, 4.4.1.1.4]

(B) Alternate Source of Power. This must be located on the premises and be a generator driven by a prime mover, another generator when the normal source is a generator, or an outside utility company when the normal source is a generator.

(C) Location of Essential Electrical System Components

517.40

Essential Electrical Systems for Nursing Homes and Limited Care Facilities

(A) Applicability

(B) Inpatient Hospital Care Facilities. If the facility provides inpatient hospital care, it must comply with the requirements of Part III, 517.30 through 517.35.

(C) Facilities Contiguous with Hospitals. These can have their systems supplied by the hospital. The reader is again referred to NFPA 99-2002 for performance, maintenance, and testing requirements.

517.41

Essential Electrical Systems

(A) General. The systems for nursing homes and limited care facilities must have two separate branches, the life safety branch and the critical branch. [NFPA99, FPN ANNEX A 4.5.2.2.1]

(B) Transfer Switches. The number of transfer switches depends on design. One transfer switch is permitted if the load is not more than 150 kVA. [NFPA99, 4.5.2.2.1]

(C) Capacity of System. The system must be capable of supplying the entire load, that is required on the essential electrical system.

(D) Separation from Other Circuits. The life safety branch must be kept separate from all other wiring and equipment. There are three exceptions.

(E) Receptacle Identification. The receptacles or cover plates must have a distinctive color or marking.

517.42

Automatic Connection to Life Safety Branch

The life safety branch must be automatically restored to power after 10 seconds of loss of the normal source of supply. This branch is referred to as the emergency system in NFPA 99-2002. The life safety branch basically supplies power for illumination of means of egress, exit signs, alarm and alerting systems, communication systems, dining and recreation areas, generator set location, and elevators. Refer to the Code for complete requirements. No function other than those listed can be connected to the life safety branch. For elevators [NFPA99, 4.4.2.2.2.2(6) and 4.5.2.2.2(7)]

517.43

Connection to Critical Branch

This section describes what must be connected to the critical branch and how it is to be energized from the essential electrical system (i.e., automatic, delayed automatic, or manual).

(A) Two Independent Sources of Power. There must be a normal source of power and an alternate source of power for use when the normal source is interrupted. [NFPA99, 4.4.1.1.4]

(B) Alternate Source of Power. This must be located on the premises and be a generator driven by a prime mover. There is an exception to this when the normal source is a generator. In that case the alternate source can be either another generator or an outside utility company. There is also an exception where battery units may be used in nursing homes or limited-care facilities meeting the requirements of Section 517.40(A), Exception. [NFPA99, 17.3.4.1, 18.3.4.1.1]

(C) Location of Essential Electrical System Components

517.45

Essential Electrical Systems for Other Health Care Facilities

(A) Essential Electrical Distribution. A battery or generator system must be used for the essential electrical distribution system. [NFPA 99-2002]

(B) Electrical Life Support Equipment. An essential electrical distribution system described in 517.30 through 517.35 must be used if electrical life support equipment is required. [NFPA 99: 14.3.4.2.1]

(C) Critical Care Areas. An essential electrical distribution system as described in 527.30 through 517.35 must be used where critical care areas are located. [NFPA99, 14.3.4.2.2]

(D) Power Systems. Battery systems must follow the requirements of Article 700 and generator systems must follow the requirements of 517.30 through 517.35.

IV. Inhalation Anesthetizing Locations

The reader is again referred to NFPA 99-2002.

517.60

Anesthetizing Location Classification

These are classified as hazardous (classified) or other-than-hazardous (classified).

517.61

Wiring and Equipment

517.62

Grounding

517.63

Grounded Power Systems in Anesthetizing Locations

517.64

Low-Voltage Equipment and Instruments

V. X-Ray Installations

517.71

Connection to Supply Circuit

517.72

Disconnecting Means

517.73

Rating of Supply Conductors and Overcurrent Protection

517.74

Control Circuit Conductors

517.75

Equipment Installations

517.76

Transformers and Capacitors

517.77

Installation of High-Tension X-Ray Cables

517.78

Guarding and Grounding

VI. Communications, Signaling Systems, Data Systems, Fire Alarm Systems, and Systems Less than 120 Volts, Nominal

517.80

Patient Care Areas

517.81

Other than Patient Care Areas

517.82

Signal Transmission between Appliances

VII. Isolated Power Systems

517.160

Isolated Power Systems

(A) Installations

(B) Line Isolation Monitor

The following article titles are listed for reference: Article 518Assembly Occupancies; Article 520Theaters, Audience Areas of Motion Picture and Television Studios, Performance Areas, and Similar Locations; Article 525Carnivals, Circuses, Fairs, and Similar Events; Article 530Motion Picture and Television Studios and Similar Locations; Article 540Motion Picture Projection Rooms; Article 545Manufactured Buildings; Article 547Agricultural Buildings; Article 550Mobile Homes, Manufactured Homes, and Mobile Home Parks; Article 551Recreational Vehicles and Recreational Vehicle Parks; Article 552Park Trailers; Article 553Floating Buildings; Article 555Marinas and Boatyards; 590Temporary Installations.

Note: Those articles in Chapters 6, 7, and 8 not discussed in their entirety are listed here with article titles for reference purposes.


Page 8

This article covers all types of wiring, equipment, grounding power supply, and equipment interconnect, in information technology equipment rooms. The reader can refer to this article as well as NFPA 75-1999 Standard for the Protection of Electronic Computer/Data Processing Equipment (whose rules this room must comply with) for further information.

645.4

Special Requirements for Information Technology Equipment Room

Article 645 will apply if all the following are met: (1) Disconnecting means are provided that are in accordance with Section 645.10; (2) a separate HVAC system is provided for the room, or another system in another area is used if fire/smoke dampers which operate from smoke detectors and operate from a disconnecting means required by Section 645.10 are provided in the ducts at the point of entry into the room; (3) the information technology equipment is listed; (4) the room is occupied only by the personnel needed to operate and maintain the equipment; (5) fire-resistant-rated walls and floors and ceilings with protected openings are used to separate the area from other areas.

645.5

Supply Circuits and Interconnecting Cables

(A) The ampacity of the branch-circuit conductors supplying units must be at least 125% of the total connected load.

(B) The data processing system can be connected to branch circuits using flexible cords and attachment plug caps not exceeding 4.5 m (15 ft.), or cord set assemblies. If a cord set assembly is used on the floor, it must be protected from physical damage.

(C) Separate units can be interconnected with cables and cable assemblies. They must be listed for this use and protected from physical damage.

(D) There are a number of rules for circuits, cables, and devices under a raised floor. Cables and receptacles are allowed to be installed under a raised floor. The area under the floor has to be accessible and the floor must be of proper construction. Branch-circuit conductors must be installed in rigid or intermediate metal conduit, rigid nonmetallic conduit, electrical metallic tubing, electrical nonmetallic tubing, metal wireway, surface metal raceway with a metal cover, nonmetallic surface raceway, nonmetallic wireway, flexible metal conduit, liquidtight flexible metal or nonmetallic conduit, Type MI cable, Type MC cable, or Type AC cable and installed in accordance with Section 300.11. The openings in the raised floor for cables have protection against abrasion to the cables and a means to minimize the debris that will fall onto the floor. The ventilation system underfloor must have smoke detection that will shut off the circulation of air when a fire or products of combustion are detected. Cables other than those listed above must be listed as type DP cable with adequate fire-resistance to be used under a raised floor. There are conditions where this is not required. Abandoned cables are permitted to remain if installed within a metal raceway

(E) All cables and accessories that are part of or used for the equipment have to be properly secured in place.

645.6

Cables Not in Information Technology Equipment Room

All cables that go outside the room have to comply with the NEC®.

Utilize Section 300.21 for rules applying to all penetrations of the fire-resistant separation of the room.

645.10

Disconnecting Means

Disconnecting means must be provided for all system equipment, HVAC equipment and fire/smoke dampers. This can be one central one or separate ones for different types of equipment. The disconnects have to be grouped together, identified, and be accessible at the principal exit. The exception is for those installations under Article 685.

645.11

Uninterruptible Power Supplies (UPS)

These are commonly referred to as UPS. These systems have to comply with Section 645.10. The disconnecting means must disconnect the battery from its load. There are two exceptions.

All exposed noncurrent-carrying metallic parts of an information technology system has to be grounded as noted in Article 250 or be double insulated. If the derived power system is in listed equipment and supplies power to systems through cable assemblies or receptacles which are part of the equipment, it is not considered a separately derived system as per Section 250.20(D). If signal reference structures are installed, they have to be bonded to the equipment grounding system of the computer equipment.

Each piece of system equipment supplied by a branch circuit must have a manufacturer's nameplate. The nameplate must show the maximum rated load in amperes, voltage, and frequency.

645.17

Power Distribution Units

Multiple panelboards are permitted in a single cabinet provided there are no more than 42 overcurrent devices in each panelboard and the power distribution unit is listed for information technology application.

The following article titles are listed for reference: Article 647Sensitive Electronic Equipment; Article 650Pipe Organs; Article 660X-Ray Equipment; Article 665Induction and Dielectric Heating Equipment; Article 668Electrolytic Cells; Article 669Electroplating; Article 670Industrial Machinery; Article 675Electrically Driven or Controlled Irrigation Machines; Article 680Swimming Pools, Fountains, and Similar Installations; Article 682Natural and Artificially Made Bodies of Water; Article 685Integrated Electrical Systems; Article 690Solar Photovoltaic Systems; Article 692Fuel Cell Systems; Article 695Fire Pumps.


Page 9

A. General

This article lays out the electrical safety requirements for the installation, operation, and maintenance of emergency systems. Emergency systems include all items necessary to deliver electricity to the load. Emergency systems are defined as those which are legally required by any governmental agency or specific code that has jurisdiction. They supply, distribute, and control electricity for power and illumination which is essential for safety to human life. The code goes into detail with specific types of occupancies and equipment. The reader is referred to other articles in this code or to other NFPA documents for additional information as follows:

NEC Article 517 Health Care Facilities for wiring and installation in health care facilities

NFPA 99-2002 Standard for Health Care Facilities for performance and maintenance in health care facilities

NFPA 101-2003 Life Safety Code for locations where the systems are essential to life safety

NFPA 110-2002 Emergency and Standby Power Systems for performance of these systems

These additional documents and articles may place other restrictions on the design of the emergency system for the specific application of the document or article.

700.2

Application of Other Articles

All applicable articles of the NEC® apply unless they are modified by this Article.

All equipment must be approved for this use.

700.4

Tests and Maintenance

(A) Conduct or Witness Test. The system must be tested at installation and periodically thereafter. The test must be conducted and witnessed by the authority having jurisdiction.

(B) Tested Periodically. To assure proper maintenance and operation the system must be tested on a schedule accepted by the authority having jurisdiction.

(C) Battery System Maintenance. Batteries, whether for systems or in conjunction with engines, must be maintained periodically.

(D) Written Record. A written record must be kept of all tests and maintenance.

(E) Testing under Load. Provisions must be made to test the system under the maximum anticipated load.

(A) Capacity and Rating. The system must be able to supply the entire load operating together. It must also be able to withstand the maximum available fault current.

(B) Selective Load Pickup, Load Shedding, and Peak Load Shaving. This permits the system to be used for various levels of loads and peak shaving provided that it can supply the emergency circuits, the legally required standby circuits, and the optional standby circuits when required.

The transfer equipment must be automatic. Interconnection of the normal and emergency sources must be prevented. Bypass means for isolation of the transfer switch are permitted. Automatic transfer switches must be electrically operated and mechanically held. Transfer equipment can supply only emergency loads.

Audible and visual signal must be installed where practical to indicate the derangement of the emergency source, that the battery is carrying the load, the battery charger is not functioning, and there is a ground fault in solidly grounded wye systems of more than 150 V to ground and circuit protective devices rated more than 1000 A. There is additional information concerning the ground-fault devices.

II. Circuit Wiring

700.9

Wiring, Emergency Systems

(A) Identification. All items in the system must be readily identified as part of the system.

(B) Wiring. The wiring of the system must be separate from the wiring of the normal system and cannot be in the same raceway, boxes, cabinets, cables, etc. There are four exceptions.

(C) Wiring Design and Location. The circuits must be designed and located to reduce to a minimum the hazards due to flooding, vandalism, icing, fires, and other adverse conditions.

(D) Fire Protection. Additional requirements are noted.

III. Sources of Power

700.12

General Requirements

The current must be available for use within 10 seconds after the loss of normal power. The supply source can be any of the following: storage batteries, generator set, separate service, uninterruptible power supply, fuel cell system, and unit equipment. Each one is covered in the code in detail as to specific requirements. Again it must be noted that some of these may not be permitted for specific occupancies as noted in other documents (i.e., health care facilities). The equipment must be designed and located so that hazards from flooding, vandalism, icing, and fires are minimized. There are requirements for buildings with certain sizes and equipment. There are also additional requirements for storage batteries, generator set, uninterruptible power supplies, fuel cell system, separate service, and unit equipment.

IV. Emergency System Circuits for Lighting and Power

700.15

Loads on Emergency Branch Circuits

Only those appliances and lamps needed for emergency use can be connected to the emergency lighting circuits.

700.16

Emergency Illumination

700.17

Circuits for Emergency Lighting

700.18

Circuits for Emergency Power

V. ControlEmergency Lighting Circuits

700.20

Switch Requirements

700.21

Switch Location

700.22

Exterior Lights

VI. Overcurrent Protection

700.25

Accessibility

700.26

Ground-Fault Protection of Equipment

This is not required for the alternate source. Ground fault indication is required in accordance with Section 700.7(D).


Page 10

A. General

This article lays out the electrical safety requirements for the installation, operation, and maintenance of legally required standby power systems. This includes all equipment necessary to deliver power to the load. The reader is referred to NFPA 99-2002 (ANSI) Standard for Health Care Facilities for additional information, NFPA 110-2002 (ANSI) Emergency and Standby Power Systems for performance information, and to ANSI/IEEE 446-1995 Recommended Practice for Emergency and Standby Power Systems for Industrial and Commercial Applications for further information.

These are systems that have this classification set by any governmental agency having jurisdiction. They are intended to supply power automatically to selected loads other than emergency system loads if the normal source fails. They differ from emergency systems in that they are not required for direct safety to life. They do supply power where the interruption might create a hazard or hamper rescue or firefighting operations. Some examples are given in the code to help the reader.

701.3

Application of Other Articles

Applicable articles of the Code apply unless otherwise modified in this Article.

Items must be approved for this use.

701.5

Test and Maintenance for Legally Required Standby Systems

(A) Conduct or Witness Test. When the installation is complete the authority having jurisdiction must either conduct or witness a test.

(B) Tested Periodically. To assure proper maintenance and operation the system must be tested on a schedule accepted by the authority having jurisdiction.

(C) Battery Systems Maintenance. Periodic maintenance is required if the batteries are used for control, starting, or ignition of a prime mover.

(D) Written Record. A written record must be kept of all tests and maintenance.

(E) Testing under Load. Provisions must be made for testing under load.

701.6

Capacity and Rating

The system must be able to supply the entire load operating together. It must also be able to withstand the available fault current.

The transfer equipment must be automatic, identified for standby use, and approved by the authority having jurisdiction. Interconnection of the normal and emergency sources must be prevented. Bypass means for isolation of the transfer switch is permitted. Automatic transfer switches have to be electrically operated and mechanically held.

Audible and visual signals must be provided to indicate the derangement of the standby source, that the standby source is carrying the load, and that the battery charger is not functioning.

The type and location of the system must be indicated on a sign at the service entrance. There is an exception for certain unit equipment. If the system is grounded to a remote grounding electrode a sign must be placed at the grounding location identifying all emergency and normal sources connected there.

II. Circuit Wiring

701.10

Wiring Legally Required Standby Systems

The wiring for this system can occupy the raceways, cables, boxes, cabinets, etc. as the general wiring.

III. Sources of Power

701.11

Legally Required Standby Power Systems

The current must be available for use within 60 seconds of the loss of the normal power. The supply system can be any one of the following: storage battery, generator set, uninterruptible power supply, separate service, connection ahead of the service disconnecting means, fuel cell system, and unit equipment. Each is covered in the code in detail as to specific requirements. Again it must be noted that some of these may not be permitted for specific occupancies as noted in other documents (i.e., health care facilities).

VI. Overcurrent Protection

701.15

Accessibility

701.17

Ground-Fault Protection of Equipment

This is not required for the alternate source.

The system must be selectively coordinated with the supply side overcurrent protection devices.


Page 11

I. General

This article applies only to the installation and operation of optional standby systems.

These systems protect business or property where life safety is not dependent on the system. Power can be supplied either automatically or manually.

702.3

Application of Other Articles

Unless modified by this article, all provisions of the Code apply.

All equipment must be approved for this use.

702.5

Capacity and Rating

The system must be able to supply the entire load operating together. It must also be able to withstand the available fault current. The user can select the load which is connected to the system.

Transfer equipment must be suitable for its use and designed and installed to prevent the inadvertent interconnection of the normal and alternate sources of power.

If it is located on the load side of branch-circuit protection, it can have supplementary overcurrent protection with an interrupting rating that can handle the generator available fault current.

There is an exception for temporary connection of a portable generator.

Audible and visual signals must be provided to indicate the derangement of the standby source and that the standby source is carrying the load.

The type and location of the system must be indicated on a sign at the service entrance. There is an exception for certain unit equipment. If the system is grounded to a remote grounding electrode a sign must be placed at the grounding location identifying all optional standby power and normal sources connected there.

II. Circuit Wiring

702.9

Wiring Optional Standby Systems

The wiring for this system can occupy the raceways, cables, boxes, etc., as the general wiring.

III. Grounding

702.10

Portable Generator Grounding

(A) Separately Derived System. Must be grounded to a grounding electrode in accordance with 250.30.

(B) Nonseparately Derived System. It must be bonded to the system grounding electrode.

IV. Sources of Power

702.11

Outdoor Generator Sets

The following article titles are listed for reference: Article 705Interconnected Electric Power Production Sources; Article 720Circuits and Equipment Operating at Less Than 50 Volts; Article 725Class 1, Class 2, and Class 3 Remote-Control, Signaling, and Power-Limited Circuits; Article 727Instrumentation Tray Cable, Type ITC; Article 760Fire Alarm Systems; Article 770Optical Fiber Cables and Raceways; Article 780Closed-Loop and Programmed Power Distribution.


Page 12

FPN No. 1: Table 1 is based on common conditions of proper cabling and alignment of conductors where the length of the pull and the number of bends are within reasonable limits. It should be recognized that, for certain conditions, a larger size conduit or a lesser conduit fill should be considered.

Table 1. Percent of Cross Section of Conduit and Tubing for Conductors

Number of Conductors

All Conductor Types

1

53

2

31

Over 2

40

FPN No. 2: When pulling three conductors or cables into a raceway, if the ratio of the raceway (inside diameter) to the conductor or cable (outside diameter) is between 2.8 and 3.2, jamming can occur. While jamming can occur when pulling four or more conductors or cables into a raceway, the probability is very low.

Article 90 Introduction

General

Wiring and Protection

Wiring Methods and Materials

Equipment for General Use

Special Occupancies

Special Equipment

  • Article 645 Information Technology Equipment

Special Conditions

Tables

Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

Annex D. Examples

  • Annex D. Examples
  • Example No. D1(a) One-Family Dwelling
  • Example No. D1(b) One-Family Dwelling
  • Example No. D2(a) Optional Calculation for One-Family Dwelling Heating Larger than Air Conditioning [See Section 220.82]
  • Example No. D2(b) Optional Calculation for One-Family Dwelling, Air Conditioning Larger than Heating [See 220.82(A) and 220.82(C)]
  • Example No. D2(c) Optional Calculation for One-Family Dwelling with Heat Pump(Single-Phase, 240/120-Volt Service) (See 220.82)
  • Example No. D3 Store Building
  • Example D3(a) Industrial Feeders in a Common Raceway
  • Example No. D4(a) Multifamily Dwelling
  • Example No. D4(b) Optional Calculation for Multifamily Dwelling
  • Example No. D5(a) Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D5(b) Optional Calculation for Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D6 Maximum Demand for Range Loads
  • Example No. D8 Motor Circuit Conductors, Overload Protection, and Short-Circuit and Ground-Fault Protection
  • Example No. D9 Feeder Ampacity Determination for Generator Field Control
  • Example No. D10 Feeder Ampacity Determination for Adjustable-Speed Drive Control [See 215.2, 430.24, 620.13, 620.14, 620.61, Tables 430.22(E), and 620.14]
  • Example No. D11 Mobile Home (See 550.18)
  • Example No. D12 Park Trailer (See 552.47)

Annex E. Types of Construction

  • Annex E. Types of Construction

show all menu


Page 13

(1) See Appendix C for the maximum number of conductors and fixture wires, all of the same size (total cross-sectional area including insulation) permitted in trade sizes of the applicable conduit or tubing.

(2) Table 1 applies only to complete conduit or tubing systems and is not intended to apply to sections of conduit or tubing used to protect exposed wiring from physical damage.

(3) Equipment grounding or bonding conductors, where installed, shall be included when calculating conduit or tubing fill. The actual dimensions of the equipment grounding or bonding conductor (insulated or bare) shall be used in the calculation.

(4) Where conduit or tubing nipples having a maximum length not to exceed 600 mm (24 inches) are installed between boxes, cabinets, and similar enclosures, the nipples shall be permitted to be filled to 60 percent of their total cross-sectional area, and Section 310.15(B)(2)(a) need not apply to this condition.

(5) For conductors not included in Chapter 9, such as multi-conductor cables, the actual dimensions shall be used.

(6) For combinations of conductors of different sizes, use Tables 5 and 5A for dimensions of conductors and Table 4 for the applicable conduit or tubing dimensions.

Table 4. Dimensions and Percent Area of Conduit and Tubing (Areas of Conduit or Tubing for the Combinations of Wires Permitted in Table 1, Chapter 9)

NEC Article 430 Part VII covers

[View Full Width]

NEC Article 430 Part VII covers

[View Full Width]

NEC Article 430 Part VII covers

[View Full Width]

NEC Article 430 Part VII covers

[View Full Width]

NEC Article 430 Part VII covers

[View Full Width]

[*] Corresponds to 356.2(2)

NEC Article 430 Part VII covers

[View Full Width]

[*] Corresponds to 356.2(1)

NEC Article 430 Part VII covers

[View Full Width]

NEC Article 430 Part VII covers

[View Full Width]

NEC Article 430 Part VII covers

[View Full Width]

NEC Article 430 Part VII covers

[View Full Width]

NEC Article 430 Part VII covers

[View Full Width]

NEC Article 430 Part VII covers

[View Full Width]

(7) When calculating the maximum number of conductors permitted in a conduit or tubing, all of the same size (total cross-sectional area including insulation), the next higher whole number shall be used to determine the maximum number of conductors permitted when the calculation results in a decimal of 0.8 or larger.

(8) Where bare conductors are permitted by other sections of this Code, the dimensions for bare conductors in Table 8 shall be permitted.

(9) A multiconductor cable of two or more conductors shall be treated as a single conductor for calculating percentage conduit fill area. For cables that have elliptical cross sections, the cross-sectional area calculation shall be based on using the major diameter of the ellipse as a circle diameter.

Table 2. Radius of Conduit and Tubing Bends

Conduit (Size)

One Shot and Full Shoe Benders

Other Bends

Metric Designator

Trade Size

mm

in.

mm

in.

16

½

101.6

4

101.6

4

21

¾

114.3

127

5

27

1

146.05

152.4

6

35

184.15

203.2

8

41

209.55

254

10

53

2

241.3

304.8

12

63

266.7

10½

381

15

78

3

330.2

13

457.2

18

91

381

15

533.4

21

103

4

406.4

16

609.6

24

129

5

609.6

24

762

30

155

6

762

30

914.4

36

Table 5. Dimensions of Insulated Conductors and Fixture Wires

Type

Size (AWG or
kcmil)

Approximate
Diameter

Approximate
Area

mm

in.

mm2

in.2

Type: FFH-2, RFH-1, RFH-2, RHH[*] , RHW[*], RHW-2[*], RHH, RHW, RHW-2,

SF-1, SF-2, SFF-1, SFF-2, TF, TFF, THHW, THW, THW-2, TW, XF, XFF

RFH-2,

18

3.454

0.136

9.355

0.0145

FFH-2

16

3.759

0.148

11.10

0.0172

RHW-2, RHH,

14

4.902

0.193

18.90

0.0293

RHW

12

5.385

0.212

22.77

0.0353

10

5.994

0.236

28.19

0.0437

8

8.280

0.326

53.87

0.0835

6

9.246

0.364

67.16

0.1041

4

10.46

0.412

86.00

0.1333

3

11.18

0.440

98.13

0.1521

2

11.99

0.472

112.9

0.1750

1

14.78

0.582

171.6

0.2660

1/0

15.80

0.622

196.1

0.3039

2/0

16.97

0.668

226.1

0.3505

3/0

18.29

0.720

262.7

0.4072

4/0

19.76

0.778

306.7

0.4754

250

22.73

0.895

405.9

0.6291

300

24.13

0.950

457.3

0.7088

350

25.43

1.001

507.7

0.7870

400

26.62

1.048

556.5

0.8626

500

28.78

1.133

650.5

1.0082

600

31.57

1.243

782.9

1.2135

700

33.38

1.314

874.9

1.3561

750

34.24

1.348

920.8

1.4272

800

35.05

1.380

965.0

1.4957

900

36.68

1.444

1057

1.6377

1000

38.15

1.502

1143

1.7719

1250

43.92

1.729

1515

2.3479

1500

47.04

1.852

1738

2.6938

1750

49.94

1.966

1959

3.0357

2000

52.63

2.072

2175

3.3719

SF-2, SFF-2

18

3.073

0.121

7.419

0.0115

 

16

3.378

0.133

8.968

0.0139

 

14

3.759

0.148

11.10

0.0172

SF-1, SFF-1

18

2.311

0.091

4.194

0.0065

RFH-1, XF, XFF

18

2.692

0.106

5.161

0.0080

TF, TFF, XF, XFF

16

2.997

0.118

7.032

0.0109

TW, XF, XFF, THHW,
THW, THW-2

14

3.378

0.133

8.968

0.0139

TW, THHW, THW,

12

3.861

0.152

11.68

0.0181

THW-2

10

4.470

0.176

15.68

0.0243

 

8

5.994

0.236

28.19

0.0437

RHH[*], RHW[*],
RHW-2[*]

14

4.140

0.163

13.48

0.0209

RHH[*], RHW[*], RHW-2[*],
XF, XFF

12

4.623

0.182

16.77

0.0260

Type RRH[*], RHW[*], RHW-2[*], THHN, THHW, THW, THW-2, TFN,

TFFN, THWN, THWN-2, XF, XFF

RHH[*], RHW[*],
RHW-2[*], XF, XFF

10

5.232

0.206

21.48

0.0333

RHH[*], RHW[*], RHW-2

8

6.756

0.266

35.87

0.0556

TW, THW,

6

7.722

0.304

46.84

0.0726

THHW,

4

8.941

0.352

62.77

0.0973

THW-2

3

9.652

0.380

73.16

0.1134

RHH[*],

2

10.46

0.412

86.00

0.1333

RHW[*]
RHW-2[*]

1

12.50

0.492

122.6

0.1901

1/0

13.51

0.532

143.4

0.2223

2/0

14.68

0.578

169.3

0.2624

3/0

16.00

0.630

201.1

0.3117

4/0

17.48

0.688

239.9

0.3718

250

19.43

0.765

296.5

0.4596

300

20.83

0.820

340.7

0.5281

350

22.12

0.871

384.4

0.5958

400

23.32

0.918

427.0

0.6619

500

25.48

1.003

509.7

0.7901

600

28.27

1.113

627.7

0.9729

700

30.07

1.184

710.3

1.1010

750

30.94

1.218

751.7

1.1652

800

31.75

1.250

791.7

1.2272

900

33.38

1.314

874.9

1.3561

1000

34.85

1.372

953.8

1.4784

1250

39.09

1.539

1200

1.8602

1500

42.21

1.662

1400

2.1695

1750

45.11

1.776

1598

2.4773

2000

47.80

1.882

1795

2.7818

TFN,

18

2.134

0.084

3.548

0.0055

TFFN

16

2.438

0.096

4.645

0.0072

THHN,

14

2.819

0.111

6.258

0.0097

THWN,

12

3.302

0.130

8.581

0.0133

THWN-2

10

4.166

0.164

13.61

0.0211

 

8

5.486

0.216

23.61

0.0366

 

6

6.452

0.254

32.71

0.0507

 

4

8.230

0.324

53.16

0.0824

 

3

8.941

0.352

62.77

0.0973

 

2

9.754

0.384

74.71

0.1158

 

1

11.33

0.446

100.8

0.1562

 

1/0

12.34

0.486

119.7

0.1855

 

2/0

13.51

0.532

143.4

0.2223

THHN, THWN,

3/0

14.83

0.584

172.8

0.2679

THWN-2

4/0

16.31

0.642

208.8

0.3237

 

250

18.06

0.711

256.1

0.3970

 

300

19.46

0.766

297.3

0.4608

Type: FEP, FEPB, PAF, PAFF, PF, PFA, PFAH, PFF, PGF, PGFF, PTF, PTFF,

TFE, THHN, THWN, THWN-2, Z, ZF, ZFF

THHN,

350

20.75

0.817

338.2

0.5242

THWN,

400

21.95

0.864

378.3

0.5863

THWN-2

500

24.10

0.949

456.3

0.7073

 

600

26.70

1.051

559.7

0.8676

 

700

28.50

1.122

637.9

0.9887

 

750

29.36

1.156

677.2

1.0496

 

800

30.18

1.188

715.2

1.1085

 

900

31.80

1.252

794.3

1.2311

 

1000

33.27

1.310

869.5

1.3478

PF, PGFF, PGF, PFF,

18

2.184

0.086

3.742

0.0058

PTF, PAF, PTFF,

16

2.489

0.098

4.839

0.0075

PAFF

         

PF, PGFF, PGF, PFF,

14

2.870

0.113

6.452

0.0100

PTF, PAF, PTFF, PAFF, TFE, FEP, PFA, FEPB, PFAH

         

TFE, FEP,

12

3.353

0.132

8.839

0.0137

PFA, FEPB,

10

3.962

0.156

12.32

0.0191

PFAH

8

5.232

0.206

21.48

0.0333

 

6

6.198

0.244

30.19

0.0468

 

4

7.417

0.292

43.23

0.0670

 

3

8.128

0.320

51.87

0.0804

 

2

8.941

0.352

62.77

0.0973

TFE, PFAH

1

10.72

0.422

90.26

0.1399

TFE, PFA

1/0

11.73

0.462

108.1

0.1676

PFAH, Z

2/0

12.90

0.508

130.8

0.2027

 

3/0

14.22

0.560

158.9

0.2463

 

4/0

15.70

0.618

193.5

0.3000

ZF, ZFF

18

1.930

0.076

2.903

0.0045

 

16

2.235

0.088

3.935

0.0061

Z, ZF, ZFF

14

2.616

0.103

5.355

0.0083

Z

12

3.099

0.122

7.548

0.0117

 

10

3.962

0.156

12.32

0.0191

 

8

4.978

0.196

19.48

0.0302

 

6

5.944

0.234

27.74

0.0430

 

4

7.163

0.282

40.32

0.0625

 

3

8.382

0.330

55.16

0.0855

 

2

9.195

0.362

66.39

0.1029

 

1

10.21

0.402

81.87

0.1269

Type: KF-1, KF-2, KFF-1, KFF-2, XHH, XHHW, XHHW-2, ZW

XHHW, ZW,

14

3.378

0.133

8.968

0.0139

XHHW-2,

12

3.861

0.152

11.68

0.0181

XHH

10

4.470

0.176

15.68

0.0243

 

8

5.994

0.236

28.19

0.0437

 

6

6.960

0.274

38.06

0.0590

 

4

8.179

0.322

52.52

0.0814

 

3

8.890

0.350

62.06

0.0962

 

2

9.703

0.382

73.94

0.1146

XHHW,

1

11.23

0.442

98.97

0.1534

XHHW-2,

1/0

12.24

0.482

117.7

0.1825

XHH

2/0

13.41

0.528

141.3

0.2190

 

3/0

14.73

0.58

170.5

0.2642

 

4/0

16.21

0.638

206.3

0.3197

 

250

17.91

0.705

251.9

0.3904

 

300

19.30

0.76

292.6

0.4536

 

350

20.60

0.811

333.3

0.5166

 

400

21.79

0.858

373.0

0.5782

 

500

23.95

0.943

450.6

0.6984

 

600

26.75

1.053

561.9

0.8709

 

700

28.55

1.124

640.2

0.9923

 

750

29.41

1.158

679.5

1.0532

 

800

30.23

1.190

717.5

1.1122

 

900

31.85

1.254

796.8

1.2351

 

1000

33.32

1.312

872.2

1.3519

 

1250

37.57

1.479

1108

1.7180

 

1500

40.69

1.602

1300

2.0157

 

1750

43.59

1.716

1492

2.3127

 

2000

46.28

1.822

1682

2.6073

KF-2,

18

1.600

0.063

2.000

0.0031

KFF-2

16

1.905

0.075

2.839

0.0044

 

14

2.286

0.090

4.129

0.0064

 

12

2.769

0.109

6.000

0.0093

 

10

3.378

0.133

8.968

0.0139

KF-1,

18

1.448

0.057

1.677

0.0026

KFF-1

16

1.753

0.069

2.387

0.0037

 

14

2.134

0.084

3.548

0.0055

 

12

2.616

0.103

5.355

0.0083

 

10

3.226

0.127

8.194

0.0127

[*] Types RHH, RHW and RHW-2 without outer covering.

Table 5A. Compact Aluminum Building Wire Nominal Dimensions[*] and Areas

NEC Article 430 Part VII covers

[View Full Width]

[*] Dimensions are from industry sources.

Table 8. Conductor Properties

NEC Article 430 Part VII covers

[View Full Width]

Table 9. Alternating-Current Resistance and Reactance for 600-Volt Cables, 3-Phase, 60 Hz, 75°C (167°F)Three Single Conductors in Conduit

NEC Article 430 Part VII covers

[View Full Width]


Page 14

For listing purposes, Tables 11(A) and 11(B) provide the required power source limitations for Class 2 and Class 3 power sources. Table 11(A) applies for alternating-current sources, and Table 11(B) applies for direct-current sources.

The power for Class 2 and Class 3 circuits shall be either (1) inherently limited requiring no overcurrent protection, or (2) not inherently limited requiring a combination of power source and overcurrent protection. Power sources designed for interconnnection shall be listed for the purpose.

As part of the listing, the Class 2 or Class 3 power source shall be durably marked where plainly visible to indicate the class of supply and its electrical rating. A Class 2 power source not suitable for wet location use shall be so marked. Exception: limited power circuits used by listed information technology equipment.

Overcurrent devices, where required, shall be located at the point where the conductor to be protected receives its supply and shall not be interchangeable with devices of higher ratings. The overcurrent device shall be permitted as an integral part of the power source.

Article 90 Introduction

General

Wiring and Protection

Wiring Methods and Materials

Equipment for General Use

Special Occupancies

Special Equipment

  • Article 645 Information Technology Equipment

Special Conditions

Tables

Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

Annex D. Examples

  • Annex D. Examples
  • Example No. D1(a) One-Family Dwelling
  • Example No. D1(b) One-Family Dwelling
  • Example No. D2(a) Optional Calculation for One-Family Dwelling Heating Larger than Air Conditioning [See Section 220.82]
  • Example No. D2(b) Optional Calculation for One-Family Dwelling, Air Conditioning Larger than Heating [See 220.82(A) and 220.82(C)]
  • Example No. D2(c) Optional Calculation for One-Family Dwelling with Heat Pump(Single-Phase, 240/120-Volt Service) (See 220.82)
  • Example No. D3 Store Building
  • Example D3(a) Industrial Feeders in a Common Raceway
  • Example No. D4(a) Multifamily Dwelling
  • Example No. D4(b) Optional Calculation for Multifamily Dwelling
  • Example No. D5(a) Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D5(b) Optional Calculation for Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D6 Maximum Demand for Range Loads
  • Example No. D8 Motor Circuit Conductors, Overload Protection, and Short-Circuit and Ground-Fault Protection
  • Example No. D9 Feeder Ampacity Determination for Generator Field Control
  • Example No. D10 Feeder Ampacity Determination for Adjustable-Speed Drive Control [See 215.2, 430.24, 620.13, 620.14, 620.61, Tables 430.22(E), and 620.14]
  • Example No. D11 Mobile Home (See 550.18)
  • Example No. D12 Park Trailer (See 552.47)

Annex E. Types of Construction

  • Annex E. Types of Construction

show all menu


Page 15

Note 1. Vmax, Imax, and VAmax are determined with the current limiting impedance in the circuit (not bypassed) as follows:

Vmax: Maximum output voltage regardless of load with rated input applied.

Imax: Maximum output current under any noncapacitive load, including short circuit, and with overcurrent protection bypassed if used. Where a transformer limits the output current, Imax limits apply after one minute of operation. Where a current-limiting impedance, listed for the purpose, or as part of a listed product, is used in combination with a nonpower-limited transformer or a stored energy source, e.g., storage battery, to limit the output current, Imax limits apply after five seconds.

VAmax: Maximum volt-ampere output after one minute of operation regardless of load and overcurrent protection bypassed if used.

Note 2. For nonsinusoidal ac, Vmax shall be not greater than 42.4 volts peak. Where wet contact (immersion not included) is likely to occur, Class 3 wiring methods shall be used or Vmax shall be not greater than 15 volts for sinusoidal ac and 21.2 volts peak for nonsinusoidal ac.

Note 3. If the power source is a transformer, (VA)max is 350 or less when Vmax is 15 or less.

Note 4. For dc interrupted at a rate of 10 to 200 Hz, Vmax shall not be greater than 24.8 volts peak. Where wet contact (immersion not included) is likely to occur, Class 3 wiring methods shall be used or Vmax shall not be greater than 30 volts for continuous dc; 12.4 volts peak for dc that is interrupted at a rate of 10 to 200 Hz.

Article 90 Introduction

General

Wiring and Protection

Wiring Methods and Materials

Equipment for General Use

Special Occupancies

Special Equipment

  • Article 645 Information Technology Equipment

Special Conditions

Tables

Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

Annex D. Examples

  • Annex D. Examples
  • Example No. D1(a) One-Family Dwelling
  • Example No. D1(b) One-Family Dwelling
  • Example No. D2(a) Optional Calculation for One-Family Dwelling Heating Larger than Air Conditioning [See Section 220.82]
  • Example No. D2(b) Optional Calculation for One-Family Dwelling, Air Conditioning Larger than Heating [See 220.82(A) and 220.82(C)]
  • Example No. D2(c) Optional Calculation for One-Family Dwelling with Heat Pump(Single-Phase, 240/120-Volt Service) (See 220.82)
  • Example No. D3 Store Building
  • Example D3(a) Industrial Feeders in a Common Raceway
  • Example No. D4(a) Multifamily Dwelling
  • Example No. D4(b) Optional Calculation for Multifamily Dwelling
  • Example No. D5(a) Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D5(b) Optional Calculation for Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D6 Maximum Demand for Range Loads
  • Example No. D8 Motor Circuit Conductors, Overload Protection, and Short-Circuit and Ground-Fault Protection
  • Example No. D9 Feeder Ampacity Determination for Generator Field Control
  • Example No. D10 Feeder Ampacity Determination for Adjustable-Speed Drive Control [See 215.2, 430.24, 620.13, 620.14, 620.61, Tables 430.22(E), and 620.14]
  • Example No. D11 Mobile Home (See 550.18)
  • Example No. D12 Park Trailer (See 552.47)

Annex E. Types of Construction

  • Annex E. Types of Construction

show all menu


Page 16

For listing purposes, Tables 12(A) and 12(B) provide the required power source limitations for power-limited fire alarm sources. Table 12(A) applies for alternating current sources, and Table 12(B) applies for direct current sources.

The power for power-limited fire alarm circuits shall be either (1) inherently limited requiring no overcurrent protection, or (2) not inherently limited requiring the power to be limited by a combination of power source and overcurrent protection.

As part of the listing, the PLFA power source shall be durably marked where plainly visible to indicate that it is a power-limited fire alarm power source.

The overcurrent device, where required, shall be located at the point where the conductor to be protected receives its supply and shall not be interchangeable with devices of higher ratings. The overcurrent device shall be permitted as an integral part of the power source.

Article 90 Introduction

General

Wiring and Protection

Wiring Methods and Materials

Equipment for General Use

Special Occupancies

Special Equipment

  • Article 645 Information Technology Equipment

Special Conditions

Tables

Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

Annex D. Examples

  • Annex D. Examples
  • Example No. D1(a) One-Family Dwelling
  • Example No. D1(b) One-Family Dwelling
  • Example No. D2(a) Optional Calculation for One-Family Dwelling Heating Larger than Air Conditioning [See Section 220.82]
  • Example No. D2(b) Optional Calculation for One-Family Dwelling, Air Conditioning Larger than Heating [See 220.82(A) and 220.82(C)]
  • Example No. D2(c) Optional Calculation for One-Family Dwelling with Heat Pump(Single-Phase, 240/120-Volt Service) (See 220.82)
  • Example No. D3 Store Building
  • Example D3(a) Industrial Feeders in a Common Raceway
  • Example No. D4(a) Multifamily Dwelling
  • Example No. D4(b) Optional Calculation for Multifamily Dwelling
  • Example No. D5(a) Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D5(b) Optional Calculation for Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D6 Maximum Demand for Range Loads
  • Example No. D8 Motor Circuit Conductors, Overload Protection, and Short-Circuit and Ground-Fault Protection
  • Example No. D9 Feeder Ampacity Determination for Generator Field Control
  • Example No. D10 Feeder Ampacity Determination for Adjustable-Speed Drive Control [See 215.2, 430.24, 620.13, 620.14, 620.61, Tables 430.22(E), and 620.14]
  • Example No. D11 Mobile Home (See 550.18)
  • Example No. D12 Park Trailer (See 552.47)

Annex E. Types of Construction

  • Annex E. Types of Construction

show all menu


Page 17

Note 1: Vmax, Imax, and VAmax are determined as follows: Vmax: Maximum output voltage regardless of load with rated input applied.

Imax: Maximum output current under any noncapacitive load, including short circuit, and with overcurrent protection bypassed if used. When a transformer limits the output current, Imax limits apply after one minute of operation. Where a current-limiting impedance, listed for the purpose, is used in combination with a nonpower-limited transformer or a stored energy source, e.g., storage battery, to limit the output current, Imax limits apply after five seconds.

Table 11(A). Class 2 and Class 3 Alternating-Current Power Source Limitations

NEC Article 430 Part VII covers

[View Full Width]

[*] Voltage ranges shown are for sinusoidal ac in indoor locations or where wet contact is not likely to occur. For nonsinusoidal or wet contact conditions, see Note 2.

Table 11(B). Class 2 and Class 3 Direct Current Power Source Limitations

NEC Article 430 Part VII covers

[View Full Width]

[*] Voltage ranges shown are for continuous dc in indoor locations or where wet contact is not likely to occur. For interrupted or wet contact conditions, see Note 4.

Table 12(A). Table PLFA Alternating-Current Power Source Limitations

NEC Article 430 Part VII covers

[View Full Width]

Table 12(B). PLFA Direct-Current Power Source Limitations

NEC Article 430 Part VII covers

[View Full Width]

VAmax: Maximum volt-ampere output after one minute of operation regardless of load and overcurrent protection bypassed if used. Current limiting impedance shall not be bypassed when determining Imax and VAmax.

Note 2. If the power source is a transformer, (VA)max is 350 or less when Vmax is 15 or less.

Article 90 Introduction

General

Wiring and Protection

Wiring Methods and Materials

Equipment for General Use

Special Occupancies

Special Equipment

  • Article 645 Information Technology Equipment

Special Conditions

Tables

Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

Annex D. Examples

  • Annex D. Examples
  • Example No. D1(a) One-Family Dwelling
  • Example No. D1(b) One-Family Dwelling
  • Example No. D2(a) Optional Calculation for One-Family Dwelling Heating Larger than Air Conditioning [See Section 220.82]
  • Example No. D2(b) Optional Calculation for One-Family Dwelling, Air Conditioning Larger than Heating [See 220.82(A) and 220.82(C)]
  • Example No. D2(c) Optional Calculation for One-Family Dwelling with Heat Pump(Single-Phase, 240/120-Volt Service) (See 220.82)
  • Example No. D3 Store Building
  • Example D3(a) Industrial Feeders in a Common Raceway
  • Example No. D4(a) Multifamily Dwelling
  • Example No. D4(b) Optional Calculation for Multifamily Dwelling
  • Example No. D5(a) Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D5(b) Optional Calculation for Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D6 Maximum Demand for Range Loads
  • Example No. D8 Motor Circuit Conductors, Overload Protection, and Short-Circuit and Ground-Fault Protection
  • Example No. D9 Feeder Ampacity Determination for Generator Field Control
  • Example No. D10 Feeder Ampacity Determination for Adjustable-Speed Drive Control [See 215.2, 430.24, 620.13, 620.14, 620.61, Tables 430.22(E), and 620.14]
  • Example No. D11 Mobile Home (See 550.18)
  • Example No. D12 Park Trailer (See 552.47)

Annex E. Types of Construction

  • Annex E. Types of Construction

show all menu


Page 18

This Annex is not part of the requirements of the NFPA document but is listed for informational purposes.

Reprinted with permission from NFPA 70-2005, the National Electrical Code®, Copyright © 2004, National Fire Protection Association, Quincy, MA 02269. This reprinted material is not the referenced subject which is represented only by the standard in its entirety.

Table

Page

C1Electrical Metallic Tubing (EMT)

305

C1(A)[*]Electrical Metallic Tubing (EMT)

310

C2Electrical Nonmetallic Tubing (ENT)

312

C2(A)[*]Electrical Nonmetallic Tubing (ENT)

317

C3Flexible Metal Conduit (FMC)

319

C3(A)[*]Flexible Metal Conduit (FMC)

324

C4Intermediate Metal Conduit (IMC)

326

C4(A)[*]Intermediate Metal Conduit (IMC)

331

C5Liquidtight Flexible Nonmetallic Conduit (Type LFNC-B)

333

C5(A)[*]Liquidtight Flexible Nonmetallic Conduit (Type LFNC-B)

338

C6Liquidtight Flexible Nonmetallic Conduit (Type LFNC-A)

340

C6(A)[*]Liquidtight Flexible Nonmetallic Conduit (Type LFNC-A)

345

C7Liquidtight Flexible Metal Conduit (LFMC)

347

C7(A)[*]Liquidtight Flexible Metal Conduit (LFMC)

352

C8Rigid Metal Conduit (RMC)

354

C8(A)[*]Rigid Metal Conduit (RMC)

362

C9Rigid PVC Conduit, Schedule 80

365

C9(A)[*]Rigid PVC Conduit, Schedule 80

373

C10Rigid PVC Conduit, Schedule 40 and HDPE Conduit

376

C10(A)[*]Rigid PVC Conduit, Schedule 40 and HDPE Conduit

383

C11Type A, Rigid PVC Conduit

386

C11(A)[*]Type A, Rigid PVC Conduit

391

C12Type EB, PVC Conduit

393

C12(A)[*]Type EB, PVC Conduit

397

[*] Where this table is used in conjunction with Tables C1 through C12, the conductors installed must be of the compact type.

Table C1. Maximum Number of Conductors or Fixture Wires in Electrical Metallic Tubing (EMT) (Based on Table 1, Chapter 9)

NEC Article 430 Part VII covers

[View Full Width]

[*] Types RHH, RHW, and RHW-2 without outer covering.

Fixture Wires

Type

Conductor Size
(AWG/kcmil)

Metric Designator (Trade Size)

16
(½)

21
(¾)

27
(1)

35
(1¼)

41
(1½)

53
(2)

FFH-2,

18

8

14

24

41

56

92

RFH-2,

16

7

12

20

34

47

78

RFHH-3

             

SF-2, SFF-2

18

10

18

30

52

71

116

 

16

8

15

25

43

58

96

 

14

7

12

20

34

47

78

SF-1, SFF-1

18

18

33

53

92

125

206

RFH-1,

18

14

24

39

68

92

152

RFHH-2, TF,

             

TFF, XF, XFF

             

RFHH-2, TF,

16

11

19

31

55

74

123

TFF, XF, XFF

             

XF, XFF

14

8

15

25

43

58

96

TFN, TFFN

18

22

38

63

108

148

244

 

16

17

29

48

83

113

186

PF, PFF, PGF,

18

21

36

59

103

140

231

PGFF, PAF,

16

16

28

46

79

108

179

PTF, PTFF,

14

12

21

34

60

81

134

PAFF

             

ZF, ZFF, ZHF,

18

27

47

77

133

181

298

HF, HFF

16

20

35

56

98

133

220

 

14

14

25

41

72

98

161

KF-2, KFF-2

18

39

69

111

193

262

433

 

16

27

48

78

136

185

305

 

14

19

33

54

93

127

209

 

12

13

23

37

64

87

144

 

10

8

15

25

43

58

96

KF-1, KFF-1

18

46

82

133

230

313

516

 

16

33

57

93

161

220

362

 

14

22

38

63

108

148

244

 

12

14

25

41

72

98

161

 

10

9

16

27

47

64

105

XF, XFF

12

4

8

13

23

31

51

 

10

3

6

10

18

24

40

Table C1(A). Maximum Number of Compact Conductors in Electrical Metallic Tubing (EMT) (Based on Table 1, Chapter 9)

NEC Article 430 Part VII covers

[View Full Width]

Table C2. Maximum Number of Conductors or Fixture Wires in Electrical Nonmetallic Tubing (ENT) (Based on Table 1, Chapter 9)

Conductors

Type

Conductor Size

(AWG/kcmil)

Metric Designator (Trade Size)

16
(½)

21
(¾)

27
(1)

35
(1¼)

41
(1½)

53
(2)

RHH, RHW,

14

3

6

10

19

26

43

RHW-2

12

2

5

9

16

22

36

10

1

4

7

13

17

29

8

1

1

3

6

9

15

6

1

1

3

5

7

12

4

1

1

2

4

6

9

3

1

1

1

3

5

8

2

0

1

1

3

4

7

1

0

1

1

1

3

5

1/0

0

0

1

1

2

4

2/0

0

0

1

1

1

3

3/0

0

0

1

1

1

3

4/0

0

0

1

1

1

2

250

0

0

0

1

1

1

300

0

0

0

1

1

1

350

0

0

0

1

1

1

400

0

0

0

1

1

1

500

0

0

0

0

1

1

600

0

0

0

0

1

1

700

0

0

0

0

0

1

750

0

0

0

0

0

1

800

0

0

0

0

0

1

900

0

0

0

0

0

1

1000

0

0

0

0

0

1

1250

0

0

0

0

0

0

1500

0

0

0

0

0

0

1750

0

0

0

0

0

0

 

2000

0

0

0

0

0

0

TW

14

7

13

22

40

55

92

 

12

5

10

17

31

42

71

 

10

4

7

13

23

32

52

 

8

1

4

7

13

17

29

RHH[*],

14

4

8

15

27

37

61

RHW[*],

             

RHW-2[*],

             

THHW,

             

THW,

             

THW-2

             

RHH[*],

12

3

7

12

21

29

49

RHW[*],

10

3

5

9

17

23

38

RHW-2[*],

             

THHW, THW

             

RHH[*],

8

1

3

5

10

14

23

RHW[*],

6

1

2

4

7

10

17

RHW-2[*],

4

1

1

3

5

8

13

TW, THW,

3

1

1

2

5

7

11

THHW,

2

1

1

2

4

6

9

THW-2

1

0

1

1

3

4

6

1/0

0

1

1

2

3

5

2/0

0

1

1

1

3

5

3/0

0

0

1

1

2

4

4/0

0

0

1

1

1

3

250

0

0

1

1

1

2

300

0

0

0

1

1

2

350

0

0

0

1

1

1

400

0

0

0

1

1

1

500

0

0

0

1

1

1

600

0

0

0

0

1

1

700

0

0

0

0

1

1

750

0

0

0

0

1

1

800

0

0

0

0

1

1

900

0

0

0

0

0

1

1000

0

0

0

0

0

1

1250

0

0

0

0

0

1

1500

0

0

0

0

0

0

1750

0

0

0

0

0

0

2000

0

0

0

0

0

0

THHN,

14

10

18

32

58

80

132

THWN,

12

7

13

23

42

58

96

THWN-2

10

4

8

15

26

36

60

8

2

5

8

15

21

35

6

1

3

6

11

15

25

4

1

1

4

7

9

15

3

1

1

3

5

8

13

2

1

1

2

5

6

11

1

1

1

1

3

5

8

1/0

0

1

1

3

4

7

2/0

0

1

1

2

3

5

3/0

0

1

1

1

3

4

4/0

0

0

1

1

2

4

250

0

0

1

1

1

3

300

0

0

1

1

1

2

350

0

0

0

1

1

2

400

0

0

0

1

1

1

500

0

0

0

1

1

1

THHN,

600

0

0

0

1

1

1

THWN,

700

0

0

0

0

1

1

THWN-2

750

0

0

0

0

1

1

 

800

0

0

0

0

1

1

 

900

0

0

0

0

1

1

 

1000

0

0

0

0

0

1

FEP, FEPB,

14

10

18

31

56

77

128

PFA, PFAH,

12

7

13

23

41

56

93

TFE

10

5

9

16

29

40

67

8

3

5

9

17

23

38

6

1

4

6

12

16

27

4

1

2

4

8

11

19

3

1

1

4

7

9

16

 

2

1

1

3

5

8

13

PFA, PFAH,

1

1

1

1

4

5

9

TFE

             

PFA, PFAH,

1/0

0

1

1

3

4

7

TFE, Z

2/0

0

1

1

2

4

6

 

3/0

0

1

1

1

3

5

 

4/0

0

1

1

1

2

4

Z

14

12

22

38

68

93

154

12

8

15

27

48

66

109

10

5

9

16

29

40

67

8

3

6

10

18

25

42

6

1

4

7

13

18

30

4

1

3

5

9

12

20

3

1

1

3

6

9

15

2

1

1

3

5

7

12

 

1

1

1

2

4

6

10

XHH,

14

7

13

22

40

55

92

XHHW,

12

5

10

17

31

42

71

XHHW-2,

10

4

7

13

23

32

52

ZW

8

1

4

7

13

17

29

6

1

3

5

9

13

21

4

1

1

4

7

9

15

3

1

1

3

6

8

13

 

2

1

1

2

5

6

11

XHH,

1

1

1

1

3

5

8

XHHW,

1/0

0

1

1

3

4

7

XHHW-2

2/0

0

1

1

2

3

6

3/0

0

1

1

1

3

5

4/0

0

0

1

1

2

4

250

0

0

1

1

1

3

300

0

0

1

1

1

3

350

0

0

1

1

1

2

400

0

0

0

1

1

1

500

0

0

0

1

1

1

600

0

0

0

1

1

1

700

0

0

0

0

1

1

750

0

0

0

0

1

1

800

0

0

0

0

1

1

900

0

0

0

0

1

1

1000

0

0

0

0

0

1

1250

0

0

0

0

0

1

1500

0

0

0

0

0

1

1750

0

0

0

0

0

0

 

2000

0

0

0

0

0

0

Note 1: This table is for concentric stranded conductors only. For compact stranded conductors, Table C2(A) should be used.

Note 2: Two-hour fire-rated RHH cable has ceramifiable insulation, which has much larger diameters than other RHH wires. Consult manufacturer's conduit fill tables.

[*] Types RHH, RHW, and RHW-2 without outer covering.

Fixture Wires

Type

Conductor Size
(AWG/kcmil)

Metric Designator (Trade Size)

16
(½)

21
(¾)

27
(1)

35
(1½)

41
(1½)

53
(2)

FFH-2,

18

6

12

21

39

53

88

RFH-2,

16

5

10

18

32

45

74

RFHH-3,

             

SF-2,

18

8

15

27

49

67

111

SFF-2

16

7

13

22

40

55

92

 

14

5

10

18

32

45

74

SF-1,

18

15

28

48

86

119

197

SFF-1

             

RFH -1,

18

11

20

35

64

88

145

RFHH -2,

             

TF, TFF,

             

XF, XFF

             

RFHH-2,

16

9

16

29

51

71

117

TF, TFF,

             

XF, XFF

             

XF, XFF

14

7

13

22

40

55

92

TFN,

18

18

33

57

102

141

233

TFFN

16

13

25

43

78

107

178

PF, PFF,

18

17

31

54

97

133

221

PGF,

16

13

24

42

75

103

171

PGFF,

14

10

18

31

56

77

128

PAF, PTF,

             

PTFF,

             

PAFF

             

ZF, ZFF,

18

22

40

70

125

172

285

ZHF, HF,

16

16

29

51

92

127

210

HFF

14

12

22

38

68

93

154

KF-2,

18

31

58

101

182

250

413

KFF-2

16

22

41

71

128

176

291

 

14

15

28

49

88

121

200

 

12

10

19

33

60

83

138

 

10

7

13

22

40

55

92

KF-1,

18

38

69

121

217

298

493

KFF-1

16

26

49

85

152

209

346

 

14

18

33

57

102

141

233

 

12

12

22

38

68

93

154

 

10

7

14

24

44

61

101

XF, XFF

12

3

7

12

21

29

49

 

10

3

5

9

17

23

38

Table C2(A). Maximum Number of Compact Conductors in Electrical Nonmetallic Tubing (ENT) (Based on Table 1, Chapter 9)

Compact Conductors

Type

Conductor Size
(AWG/kcmil)

Metric Designator (Trade Size)

16
(½)

21
(¾)

27
(1)

35
(1¼)

41
(1½)

53
(2)

THW,

8

1

3

6

11

15

25

THW-2,

6

1

2

4

8

11

19

THHW

4

1

1

3

6

8

14

2

1

1

2

4

6

10

1

0

1

1

3

4

7

1/0

0

1

1

3

4

6

2/0

0

1

1

2

3

5

3/0

0

1

1

1

3

4

4/0

0

0

1

1

2

4

250

0

0

1

1

1

3

300

0

0

1

1

1

2

350

0

0

0

1

1

2

400

0

0

0

1

1

1

500

0

0

0

1

1

1

600

0

0

0

1

1

1

700

0

0

0

0

1

1

750

0

0

0

0

1

1

900

0

0

0

0

1

1

 

1000

0

0

0

0

0

1

THHN,

8

THWN,

6

1

4

7

12

17

28

THWN-2

4

1

2

4

7

10

17

2

1

1

3

5

7

12

1

1

1

2

4

5

9

1/0

1

1

1

3

5

8

2/0

0

1

1

3

4

6

3/0

0

1

1

2

3

5

4/0

0

1

1

1

2

4

250

0

0

1

1

1

3

300

0

0

1

1

1

3

350

0

0

1

1

1

2

400

0

0

0

1

1

2

500

0

0

0

1

1

1

600

0

0

0

1

1

1

 

700

0

0

0

1

1

1

THHN,

750

0

0

0

1

1

1

THWN,

900

0

0

0

0

1

1

THWN-2

1000

0

0

0

0

1

1

XHHW,

8

2

4

8

14

19

32

XHHW-2

6

1

3

6

10

14

24

4

1

2

4

7

10

17

2

1

1

3

5

7

12

1

1

1

2

4

5

9

1/0

1

1

1

3

5

8

2/0

0

1

1

3

4

7

3/0

0

1

1

2

3

5

4/0

0

1

1

1

3

4

250

0

0

1

1

1

3

300

0

0

1

1

1

3

350

0

0

1

1

1

3

400

0

0

1

1

1

2

500

0

0

0

1

1

1

600

0

0

0

1

1

1

700

0

0

0

1

1

1

750

0

0

0

1

1

1

900

0

0

0

0

1

1

 

1000

0

0

0

0

1

1

Definition: Compact stranding is the result of a manufacturing process where the standard conductor is compressed to the extent that the interstices (voids between strand wires) are virtually climated.

Table C3. Maximum Number of Conductors or Fixture Wires in Flexible Metal Conduit (FMC) (Based on Table 1, Chapter 9)

NEC Article 430 Part VII covers

[View Full Width]

[*] Types RHH, RHW, and RHW-2 without outer covering.

Fixture Wires

Type

Conductor Size
(AWG/kcmil)

Metric Designator (Trade Size)

16
(½)

21
(¾)

27
(1)

35
(1½)

41
(1½)

53
(2)

FFH-2,

18

8

14

22

35

51

90

RFH-2,

16

7

12

19

29

43

76

RFHH-3

             

SF-2,

18

11

18

28

44

64

113

SFF-2

16

9

15

23

36

53

94

 

14

7

12

19

29

43

76

SF-1,

18

19

32

50

78

114

201

SFF-1

             

RFH-1,

18

14

24

37

58

84

148

RFHH-2,

             

TF, TFF,

             

XF, XFF

             

RFHH-2,

16

11

19

30

47

68

120

TF, TFF,

             

XF, XFF

             

XF, XFF

14

9

15

23

36

53

94

TFN,

18

23

38

59

93

135

237

TFFN

16

17

29

45

71

103

181

PF, PFF,

18

22

36

56

88

128

225

PGF,

16

17

28

43

68

99

174

PGFF,

14

12

21

32

51

74

130

PAF, PTF,

             

PTFF,

             

PAFF

             

ZF, ZFF,

18

28

47

72

113

165

290

ZHF, HF,

16

20

35

53

83

121

214

HFF

14

15

25

39

61

89

157

KF-2,

18

41

68

105

164

239

421

KFF-2

16

28

48

74

116

168

297

 

14

19

33

51

80

116

204

 

12

13

23

35

55

80

140

 

10

9

15

23

36

53

94

KF-1,

18

48

82

125

196

285

503

KFF-1

16

34

57

88

138

200

353

 

14

23

38

59

93

135

237

 

12

15

25

39

61

89

157

 

10

10

16

25

40

58

103

XF, XFF

12

5

8

12

19

28

50

 

10

4

6

10

15

22

39

Table C3(A). Maximum Number of Compact Conductors in Flexible Metal Conduit (FMC) (Based on Table 1, Chapter 9)

NEC Article 430 Part VII covers

[View Full Width]

Table C4. Maximum Number of Conductors or Fixture Wires in Intermediate Metal Conduit (IMC) (Based on Table 1, Chapter 9)

NEC Article 430 Part VII covers

[View Full Width]

[5] Types RHH, RHW, and RHW-2 without outer covering.

Fixture Wires

Type

Conductor Size
(AWG/kcmil)

Metric Designator (Trade Size)

16
(½)

21
(¾)

27
(1)

35
(1¼)

41
(1½)

53
(2)

FHH-2,

18

9

16

26

45

61

100

RFH-2,

16

8

13

22

38

51

84

RFHH-3

             

SF-2,

18

12

20

33

57

77

126

SFF-2

16

10

17

27

47

64

104

 

14

8

13

22

38

51

84

SF-1,

18

21

36

59

101

137

223

SFF-1

             

RFH-1,

18

15

26

43

75

101

165

RFHH-2,

             

TF, TFF,

             

XF, XFF

             

RFH-2,

16

12

21

35

60

81

133

TF, TFF,

             

XF, XFF

             

XF, XFF

14

10

17

27

47

64

104

TFN,

18

25

42

69

119

161

264

TFFN

16

19

32

53

91

123

201

PF, PFF,

18

23

40

66

113

153

250

PGF,

16

18

31

51

87

118

193

PGFF,

14

13

23

38

66

89

145

PAF,

             

PTF,

             

PTFF,

             

PAFF

             

ZF, ZFF,

18

30

52

85

146

197

322

ZHF, HF,

16

22

38

63

108

145

238

HFF

14

16

28

46

79

107

175

KF-2,

18

44

75

123

212

287

468

KFF-2

16

31

53

87

149

202

330

 

14

21

36

60

103

139

227

 

12

14

25

41

70

95

156

 

10

10

17

27

47

64

104

KF-1,

18

52

90

147

253

342

558

KFF-1

16

37

63

103

178

240

392

 

14

25

42

69

119

161

264

 

12

16

28

46

79

107

175

 

10

10

18

30

52

70

114

XF, XFF

12

5

9

14

25

34

56

 

10

4

7

11

19

26

43

Table C4(A). Maximum Number of Compact Conductors in Intermediate Metal Conduit (IMC) (Based on Table 1, Chapter 9)

NEC Article 430 Part VII covers

[View Full Width]

Table C5. Maximum Number of Conductors or Fixture Wires in Liquidtight Flexible Nonmetallic Conduit (Type LFNC-B[*]) (Based on Table 1, Chapter 9)

Conductors

Type

Conductor size

(AWG/kcmil)

Metric Designator (Trade Size)

12
(3/8)

16
(½)

21
(¾)

27
(1)

35
(1¼)

41
(1½)

53
(2)

RHH,

14

2

4

7

12

21

27

44

RHW,

12

1

3

6

10

17

22

36

RHW-2

10

1

3

5

8

14

18

29

 

8

1

1

2

4

7

9

15

 

6

1

1

1

3

6

7

12

 

4

0

1

1

2

4

6

9

 

3

0

1

1

1

4

5

8

 

2

0

1

1

1

3

4

7

 

1

0

0

1

1

1

3

5

 

1/0

0

0

1

1

1

2

4

 

2/0

0

0

1

1

1

1

3

 

3/0

0

0

0

1

1

1

3

 

4/0

0

0

0

1

1

1

2

 

250

0

0

0

0

1

1

1

 

300

0

0

0

0

1

1

1

 

350

0

0

0

0

1

1

1

 

400

0

0

0

0

1

1

1

 

500

0

0

0

0

1

1

1

 

600

0

0

0

0

0

1

1

 

700

0

0

0

0

0

0

1

 

750

0

0

0

0

0

0

1

 

800

0

0

0

0

0

0

1

 

900

0

0

0

0

0

0

1

 

1000

0

0

0

0

0

0

1

 

1250

0

0

0

0

0

0

0

 

1500

0

0

0

0

0

0

0

 

1750

0

0

0

0

0

0

0

 

2000

0

0

0

0

0

0

0

TW,

14

5

9

15

25

44

57

93

 

12

4

7

12

19

33

43

71

 

10

3

5

9

14

25

32

53

 

8

1

3

5

8

14

18

29

RHH[

NEC Article 430 Part VII covers
],

14

3

6

10

16

29

38

62

RHW[

NEC Article 430 Part VII covers
],

           

RHW-2[

NEC Article 430 Part VII covers
],

           

THHW,

           

THW,

           

THW-2

               

RHH[

NEC Article 430 Part VII covers
],

12

3

5

8

13

23

30

50

RHW[

NEC Article 430 Part VII covers
],

10

1

3

6

10

18

23

39

RHW-2[

NEC Article 430 Part VII covers
],

           

THHW,

           

THW

               

RHH[

NEC Article 430 Part VII covers
],

8

1

1

4

6

11

14

23

RHW[

NEC Article 430 Part VII covers
],

             

RHW-2[

NEC Article 430 Part VII covers
],

             

THHW,

             

THW,

             

THW-2

               

RHH[

NEC Article 430 Part VII covers
],

6

1

1

3

5

8

11

18

RHW[

NEC Article 430 Part VII covers
],

4

1

1

1

3

6

8

13

RHW-2[

NEC Article 430 Part VII covers
],

3

1

1

1

3

5

7

11

TW,

2

0

1

1

2

4

6

9

THW,

1

0

1

1

1

3

4

7

THHW,

1/0

0

0

1

1

2

3

6

THW-2

2/0

0

0

1

1

2

3

5

 

3/0

0

0

1

1

1

2

4

 

4/0

0

0

0

1

1

1

3

 

250

0

0

0

1

1

1

3

 

300

0

0

0

1

1

1

2

 

350

0

0

0

0

1

1

1

 

400

0

0

0

0

1

1

1

 

500

0

0

0

0

1

1

1

 

600

0

0

0

0

1

1

1

 

700

0

0

0

0

0

1

1

 

750

0

0

0

0

0

1

1

 

800

0

0

0

0

0

1

1

 

900

0

0

0

0

0

0

1

 

1000

0

0

0

0

0

0

1

 

1250

0

0

0

0

0

0

1

 

1500

0

0

0

0

0

0

0

 

1750

0

0

0

0

0

0

0

 

2000

0

0

0

0

0

0

0

THHN,

14

8

13

22

36

63

81

133

THWN,

12

5

9

16

26

46

59

97

THWN-2

10

3

6

10

16

29

37

61

 

8

1

3

6

9

16

21

35

 

6

1

2

4

7

12

15

25

 

4

1

1

2

4

7

9

15

 

3

1

1

1

3

6

8

13

 

2

1

1

1

3

5

7

11

 

1

0

1

1

1

4

5

8

THHN,

1/0

0

1

1

1

3

4

7

THWN,

2/0

0

0

1

1

2

3

6

THWN-2

3/0

0

0

1

1

1

3

5

 

4/0

0

0

1

1

1

2

4

 

250

0

0

0

1

1

1

3

 

300

0

0

0

1

1

1

3

 

350

0

0

0

1

1

1

2

 

400

0

0

0

0

1

1

1

 

500

0

0

0

0

1

1

1

 

600

0

0

0

0

1

1

1

 

700

0

0

0

0

1

1

1

 

750

0

0

0

0

0

1

1

 

800

0

0

0

0

0

1

1

 

900

0

0

0

0

0

1

1

 

1000

0

0

0

0

0

0

1

FEP,

14

7

12

21

35

61

79

129

FEPB,

12

5

9

15

25

44

57

94

PFA,

10

4

6

11

18

32

41

68

PFAH,

8

1

3

6

10

18

23

39

TFE

6

1

2

4

7

13

17

27

 

4

1

1

3

5

9

12

19

 

3

1

1

2

4

7

10

16

 

2

1

1

1

3

6

8

13

PFA,

1

0

1

1

2

4

5

9

PFAH,

             

TFE

               

PFA,

1/0

0

1

1

1

3

4

7

PFAH

               

TFE,Z

2/0

0

1

1

1

3

4

6

 

3/0

0

0

1

1

2

3

5

 

4/0

0

0

1

1

1

2

4

Z

14

9

15

26

42

73

95

156

 

12

6

10

18

30

52

67

111

 

10

4

6

11

18

32

41

68

 

8

2

4

7

11

20

26

43

 

6

1

3

5

8

14

18

30

 

4

1

1

3

5

9

12

20

 

3

1

1

2

4

7

9

15

 

2

0

1

1

3

6

7

12

 

1

0

1

1

2

5

6

10

XHH,

14

5

9

15

25

44

57

93

XHHW,

12

4

7

12

19

33

43

71

XHHW-2,

10

3

5

9

14

25

32

53

ZW

8

1

3

5

8

14

18

29

 

6

1

1

3

6

10

13

22

XHH,

4

1

1

2

4

7

9

16

XHHW,

3

1

1

1

3

6

8

13

XHHW-2,

2

1

1

1

3

5

7

11

ZW

               

XHH,

1

0

1

1

1

4

5

8

XHHW,

1/0

0

1

1

1

3

4

7

XHHW-2

2/0

0

0

1

1

2

3

6

 

3/0

0

0

1

1

1

3

5

 

4/0

0

0

1

1

1

2

4

 

250

0

0

0

1

1

1

3

 

300

0

0

0

1

1

1

3

 

350

0

0

0

1

1

1

2

 

400

0

0

0

0

1

1

1

 

500

0

0

0

0

1

1

1

 

600

0

0

0

0

1

1

1

 

700

0

0

0

0

1

1

1

 

750

0

0

0

0

0

1

1

 

800

0

0

0

0

0

1

1

 

900

0

0

0

0

0

1

1

 

1000

0

0

0

0

0

0

1

 

1250

0

0

0

0

0

0

1

 

1500

0

0

0

0

0

0

1

 

1750

0

0

0

0

0

0

0

 

2000

0

0

0

0

0

0

0

Fixture Wires

FFH-2,

18

5

8

15

24

42

54

89

RFH-2

16

4

7

12

20

35

46

75

SF-2,

18

6

11

19

30

53

69

113

SFF-2

16

5

9

15

25

44

57

93

 

14

4

7

12

20

35

46

75

SF-1,

18

11

19

33

53

94

122

199

SFF-1

               

RFH-1,

18

8

14

24

39

69

90

147

RFHH-2,

               

TF, TFF,

               

XF, XFF

               

RFHH-2,

16

7

11

20

32

56

72

119

TF, TFF,

               

XF, XFF

               

XF, XFF

14

5

9

15

25

44

57

93

TFN,

18

14

23

39

63

111

144

236

TFFN

16

10

17

30

48

85

110

180

PF,PFF,

18

13

21

37

60

105

136

223

PGF,

16

10

16

29

46

81

105

173

PGFF,

14

7

12

21

35

61

79

129

PAF,

             

PTF,

             

PTFF,

             

PAFF

               

HF,HFF,

18

17

28

48

77

136

176

288

ZF,ZFF,

16

12

20

35

57

100

129

212

ZHF

14

9

15

26

42

73

95

156

KF-2,

18

24

40

70

112

197

255

418

KFF-2

16

17

28

49

79

139

180

295

 

14

12

19

34

54

95

123

202

 

12

8

13

23

37

65

85

139

 

10

5

9

15

25

44

57

93

KF-1,

18

29

48

83

134

235

304

499

KFF-1

16

20

34

58

94

165

214

350

 

14

14

23

39

63

111

144

236

 

12

9

15

26

42

73

95

156

 

10

6

10

17

27

48

62

102

XF,XFF

12

3

5

8

13

23

30

50

 

10

1

3

6

10

18

23

39

Note 1: This table is for concentric stranded conductors only. For compact stranded conductors, Table C5(A) should be used.

Note 2: Two-hour fire-rated RHH cable has ceramifiable insulation, which has much larger diameters than other RHH wires. Consult manufacturer's conduit fill tables.

[*] Corresponds to 356.2(2).

[

NEC Article 430 Part VII covers
images/ent/U2020.GIF border=0>] Types RHH, RHW, and RHW-2 without outer covering.

Table C5(A). Maximum Number of Compact Conductors in Liquidtight Flexible Nonmetallic Conduit (Type LFNC-B[*]) (Based on Table 1, Chapter 9)

Compact Conductors

Type

Conductor size

(AWG/kcmil)

Metric Designator (Trade Size)

12
(3/8)

16
(½)

21
(¾)

27
(1)

35
(1¼)

41
(1½)

53
(2)

THW,

8

1

2

4

7

12

15

25

THW-2,

6

1

1

3

5

9

12

19

THHW

4

1

1

2

4

7

9

14

 

2

1

1

1

3

5

6

11

 

1

0

1

1

1

3

4

7

 

1/0

0

1

1

1

3

4

6

 

2/0

0

0

1

1

2

3

5

 

3/0

0

0

1

1

1

3

4

 

4/0

0

0

1

1

1

2

4

 

250

0

0

0

1

1

1

3

 

300

0

0

0

1

1

1

2

 

350

0

0

0

1

1

1

2

 

400

0

0

0

0

1

1

1

 

500

0

0

0

0

1

1

1

 

600

0

0

0

0

1

1

1

 

700

0

0

0

0

1

1

1

 

750

0

0

0

0

0

1

1

 

900

0

0

0

0

0

1

1

 

1000

0

0

0

0

0

1

1

THHN,

8

THWN,

6

1

2

4

7

13

17

28

THWN-2

4

1

1

3

4

8

11

17

 

2

1

1

1

3

6

7

12

 

1

0

1

1

2

4

6

9

 

1/0

0

1

1

1

4

5

8

 

2/0

0

1

1

1

3

4

6

 

3/0

0

0

1

1

2

3

5

 

4/0

0

0

1

1

1

3

4

 

250

0

0

1

1

1

1

3

 

300

0

0

0

1

1

1

3

 

350

0

0

0

1

1

1

2

 

400

0

0

0

1

1

1

2

 

500

0

0

0

0

1

1

1

 

600

0

0

0

0

1

1

1

 

700

0

0

0

0

1

1

1

 

750

0

0

0

0

1

1

1

 

900

0

0

0

0

0

1

1

 

1000

0

0

0

0

0

1

1

XHHW,

8

1

3

5

9

15

20

33

XHHW-2

6

1

2

4

6

11

15

24

 

4

1

1

3

4

8

11

17

 

2

1

1

1

3

6

7

12

 

1

0

1

1

2

4

6

9

XHHW,

1/0

0

1

1

1

4

5

8

XHHW-2

2/0

0

1

1

1

3

4

7

 

3/0

0

0

1

1

2

3

5

 

4/0

0

0

1

1

1

3

4

 

250

0

0

1

1

1

1

3

 

300

0

0

0

1

1

1

3

 

350

0

0

0

1

1

1

3

 

400

0

0

0

1

1

1

2

 

500

0

0

0

0

1

1

1

 

600

0

0

0

0

1

1

1

 

700

0

0

0

0

1

1

1

 

750

0

0

0

0

1

1

1

 

900

0

0

0

0

0

1

1

 

1000

0

0

0

0

0

1

1

Definition: Compact stranding is the result of a manufacturing process where the standard conductor is compressed to the extent that the interstices (voids between strand wires) are virtually eliminated.

[*] Corresponds to 356.2(2).

Table C6. Maximun Number of Conductors or Fixture Wires in Liquidtight Flexible Nonmetallic Conduit (Type LFNC-A[*]) (Based on Table 1, Chapter 9)

Conductors

Type

Conductor size
(AWG/kcmil)

Metric Designator (Trade Size)

12
(3/8)

16
(½)

21
(¾)

27
(1)

35
(1¼)

41
(1½)

53
(2)

RHH,

14

2

4

7

11

20

27

45

RHW,

12

1

3

6

9

17

23

38

RHW-2

10

1

3

5

8

13

18

30

 

8

1

1

2

4

7

9

16

 

6

1

1

1

3

5

7

13

 

4

0

1

1

2

4

6

10

 

3

0

1

1

1

4

5

8

 

2

0

1

1

1

3

4

7

 

1

0

0

1

1

1

3

5

 

1/0

0

0

1

1

1

2

4

 

2/0

0

0

1

1

1

1

4

 

3/0

0

0

0

1

1

1

3

 

4/0

0

0

0

1

1

1

3

 

250

0

0

0

0

1

1

1

 

300

0

0

0

0

1

1

1

 

350

0

0

0

0

1

1

1

 

400

0

0

0

0

1

1

1

 

500

0

0

0

0

0

1

1

 

600

0

0

0

0

0

1

1

 

700

0

0

0

0

0

0

1

 

750

0

0

0

0

0

0

1

 

800

0

0

0

0

0

0

1

 

900

0

0

0

0

0

0

1

 

1000

0

0

0

0

0

0

1

 

1250

0

0

0

0

0

0

0

 

1500

0

0

0

0

0

0

0

 

1750

0

0

0

0

0

0

0

 

2000

0

0

0

0

0

0

0

TW

14

5

9

15

24

43

58

96

 

12

4

7

12

19

33

44

74

 

10

3

5

9

14

24

33

55

 

8

1

3

5

8

13

18

30

RHH[

NEC Article 430 Part VII covers
],

14

3

6

10

16

28

38

64

RHW[

NEC Article 430 Part VII covers
],

               

RHW-2[

NEC Article 430 Part VII covers
],

               

THHW,

               

THW,

               

THW-2

               

RHH[

NEC Article 430 Part VII covers
],

12

3

4

8

13

23

31

51

RHW[

NEC Article 430 Part VII covers
],

10

1

3

6

10

18

24

40

RHW-2[

NEC Article 430 Part VII covers
],

               

THHW,

               

THW

               

RHH[

NEC Article 430 Part VII covers
],

8

1

1

4

6

10

14

24

RHW[

NEC Article 430 Part VII covers
],

               

RHW-2[

NEC Article 430 Part VII covers
],

               

THHW,

               

THW,

               

THW-2

               

RHH[

NEC Article 430 Part VII covers
],

6

1

1

3

4

8

11

18

RHW[

NEC Article 430 Part VII covers
],

4

1

1

1

3

6

8

13

RHW-2[

NEC Article 430 Part VII covers
],

3

1

1

1

3

5

7

11

TW,THW,

2

0

1

1

2

4

6

10

THHW,

1

0

1

1

1

3

4

7

THW-2

               
 

1/0

0

0

1

1

2

3

6

 

2/0

0

0

1

1

1

3

5

 

3/0

0

0

1

1

1

2

4

 

4/0

0

0

0

1

1

1

3

 

250

0

0

0

1

1

1

3

 

300

0

0

0

1

1

1

2

 

350

0

0

0

0

1

1

1

 

400

0

0

0

0

1

1

1

 

500

0

0

0

0

1

1

1

 

600

0

0

0

0

1

1

1

 

700

0

0

0

0

0

1

1

 

750

0

0

0

0

0

1

1

 

800

0

0

0

0

0

1

1

 

900

0

0

0

0

0

0

1

 

1000

0

0

0

0

0

0

1

 

1250

0

0

0

0

0

0

1

 

1500

0

0

0

0

0

0

1

 

1750

0

0

0

0

0

0

0

 

2000

0

0

0

0

0

0

0

THHN,

14

8

13

22

35

62

83

137

THWN,

12

5

9

16

25

45

60

100

THWN-2

10

3

6

10

16

28

38

63

 

8

1

3

6

9

16

22

36

 

6

1

2

4

6

12

16

26

 

4

1

1

2

4

7

9

16

 

3

1

1

1

3

6

8

13

 

2

1

1

1

3

5

7

11

 

1

0

1

1

1

4

5

8

 

1/0

0

1

1

1

3

4

7

 

2/0

0

0

1

1

2

3

6

 

3/0

0

0

1

1

1

3

5

 

4/0

0

0

1

1

1

2

4

THHN,

250

0

0

0

1

1

1

3

THWN,

300

0

0

0

1

1

1

3

THWN-2

350

0

0

0

1

1

1

2

 

400

0

0

0

0

1

1

1

 

500

0

0

0

0

1

1

1

 

600

0

0

0

0

1

1

1

 

700

0

0

0

0

1

1

1

 

750

0

0

0

0

0

1

1

 

800

0

0

0

0

0

1

1

 

900

0

0

0

0

0

1

1

 

1000

0

0

0

0

0

0

1

FEP,

14

7

12

21

34

60

80

133

FEPB,

12

5

9

15

25

44

59

97

PFA,

10

4

6

11

18

31

42

70

PFAH,

8

1

3

6

10

18

24

40

TFE

6

1

2

4

7

13

17

28

 

4

1

1

3

5

9

12

20

 

3

1

1

2

4

7

10

16

 

2

1

1

1

3

6

8

13

PFA,

1

0

1

1

2

4

5

9

PFAH,

               

TFE

               

PFA,

1/0

0

1

1

1

3

5

8

PFAH,

2/0

0

1

1

1

3

4

6

TFE,Z

3/0

0

0

1

1

2

3

5

 

4/0

0

0

1

1

1

2

4

Z

14

9

15

25

41

72

97

161

 

12

6

10

18

29

51

69

114

 

10

4

6

11

18

31

42

70

 

8

2

4

7

11

20

26

44

 

6

1

3

5

8

14

18

31

 

4

1

1

3

5

9

13

21

 

3

1

1

2

4

7

9

15

 

2

1

1

1

3

6

8

13

 

1

1

1

1

2

4

6

10

XHH,

14

5

9

15

24

43

58

96

XHHW,

12

4

7

12

19

33

44

74

XHHW-2,

10

3

5

9

14

24

33

55

ZW

8

1

3

5

8

13

18

30

 

6

1

1

3

5

10

13

22

 

4

1

1

2

4

7

10

16

 

3

1

1

1

3

6

8

14

 

2

1

1

1

3

5

7

11

XHH,

1

0

1

1

1

4

5

8

XHHW,

1/0

0

1

1

1

3

4

7

XHHW-2

2/0

0

0

1

1

2

3

6

 

3/0

0

0

1

1

1

3

5

 

4/0

0

0

1

1

1

2

4

 

250

0

0

0

1

1

1

3

 

300

0

0

0

1

1

1

3

 

350

0

0

0

1

1

1

2

 

400

0

0

0

0

1

1

1

 

500

0

0

0

0

1

1

1

 

600

0

0

0

0

1

1

1

 

700

0

0

0

0

1

1

1

 

750

0

0

0

0

0

1

1

 

800

0

0

0

0

0

1

1

 

900

0

0

0

0

0

1

1

 

1000

0

0

0

0

0

0

1

 

1250

0

0

0

0

0

0

1

 

1500

0

0

0

0

0

0

1

 

1750

0

0

0

0

0

0

0

 

2000

0

0

0

0

0

0

0

Fixture Wires

FFH-2,

18

5

8

14

23

41

55

92

RFH-2

16

4

7

12

20

35

47

77

SF-2,

18

6

11

18

29

52

70

116

SFF-2

16

5

9

15

24

43

58

96

 

14

4

7

12

20

35

47

77

SF-1,

18

12

19

33

52

92

124

205

SFF-1

               

RFH-1,

18

8

14

24

39

68

91

152

RFHH-2,

               

TF,TFF,

               

XF,XFF

               

RFHH-2,

16

7

11

19

31

55

74

122

TF,TFF,

               

XF,XFF

               

XF,XFF

14

5

9

15

24

43

58

96

TFN,TFFN

18

14

22

39

62

109

146

243

 

16

10

17

29

47

83

112

185

PF,PFF,

18

13

21

37

59

103

139

230

PGF,

16

10

16

28

45

80

107

178

PGFF,

14

7

12

21

34

60

80

133

PAF,PTF,

               

PTFF,

               

PAFF

               

HF,HFF,

18

17

27

47

76

133

179

297

ZF,ZFF,

16

12

20

35

56

98

132

219

ZHF

14

9

15

25

41

72

97

161

KF-2,

18

25

40

69

110

193

260

431

KFF-2

16

17

28

48

77

136

183

303

 

14

12

19

33

53

94

126

209

 

12

8

13

23

36

64

86

143

 

10

5

9

15

24

43

58

96

KF-1,

18

29

48

82

131

231

310

514

KFF-1

16

21

33

57

92

162

218

361

 

14

14

22

39

62

109

146

243

 

12

9

15

25

41

72

97

161

 

10

6

10

17

27

47

63

105

XF,XFF

12

3

4

8

13

23

31

51

 

10

1

3

6

10

18

24

40

Note 1: This table is for concentric stranded conductors only. For compact stranded conductors, Table C6(A) should be used.

Note 2: Two-hour fire-rated RHH cable has ceramifiable insulation, which has much larger diameters than other RHH wires. Consult manufacturer's conduit fill tables.

[*] Corresponds to 356.2(1).

[images/ent/U2020.GIF border=0>] Types RHH, RHW, and RHW-2 without outer covering.

Table C6(A). Maximum Number of Compact Conductors in Liquidtight Flexible Nonmetallic Conduit (Type LFNC-A[*]) (Based on Table 1, Chapter 9)

Compact Conductors

Type

Conductor size
(AWG/kcmil)

Metric Designator (Trade Size)

12
(3/8)

16
(½)

21
(¾)

27
(1)

35
(1¼)

41
(1½)

53
(2)

THW,

8

1

2

4

6

11

16

26

THW-2,

6

1

1

3

5

9

12

20

THHW

4

1

1

2

4

7

9

15

 

2

1

1

1

3

5

6

11

 

1

0

1

1

1

3

4

8

 

1/0

0

1

1

1

3

4

7

 

2/0

0

0

1

1

2

3

5

 

3/0

0

0

1

1

1

3

5

 

4/0

0

0

1

1

1

2

4

 

250

0

0

0

1

1

1

3

 

300

0

0

0

1

1

1

3

 

350

0

0

0

1

1

1

2

 

400

0

0

0

0

1

1

1

 

500

0

0

0

0

1

1

1

 

600

0

0

0

0

1

1

1

 

700

0

0

0

0

1

1

1

 

750

0

0

0

0

0

1

1

 

900

0

0

0

0

0

1

1

 

1000

0

0

0

0

0

1

1

THHN,

8

THWN,

6

1

2

4

7

13

18

29

THWN-2

4

1

1

3

4

8

11

18

 

2

1

1

1

3

6

8

13

 

1

0

1

1

2

4

6

10

 

1/0

0

1

1

1

3

5

8

 

2/0

0

1

1

1

3

4

7

 

3/0

0

0

1

1

2

3

6

 

4/0

0

0

1

1

1

3

5

 

250

0

0

1

1

1

1

3

 

300

0

0

0

1

1

1

3

 

350

0

0

0

1

1

1

3

 

400

0

0

0

1

1

1

2

 

500

0

0

0

0

1

1

1

 

600

0

0

0

0

1

1

1

 

700

0

0

0

0

1

1

1

 

750

0

0

0

0

1

1

1

 

900

0

0

0

0

0

1

1

 

1000

0

0

0

0

0

1

1

XHHW,

8

1

3

5

8

15

20

34

XHHW-2

6

1

2

4

6

11

15

25

 

4

1

1

3

4

8

11

18

 

2

1

1

1

3

6

8

13

 

1

0

1

1

2

4

6

10

 

1/0

0

1

1

1

3

5

8

 

2/0

0

1

1

1

3

4

7

 

3/0

0

0

1

1

2

3

6

 

4/0

0

0

1

1

1

3

5

 

250

0

0

1

1

1

2

4

 

300

0

0

0

1

1

1

3

 

350

0

0

0

1

1

1

3

 

400

0

0

0

1

1

1

2

 

500

0

0

0

0

1

1

1

 

600

0

0

0

0

1

1

1

 

700

0

0

0

0

1

1

1

 

750

0

0

0

0

1

1

1

 

900

0

0

0

0

0

1

1

 

1000

0

0

0

0

0

1

1

Definition: Compact stranding is the result of a manufacturing process where the standard conductor is compressed to the extent that the interstices (voids between strand wires) are virtually eliminated.

[*] Corresponds to 356.2(1).

Table C7. Maximum Number of Conductors or Fixture Wires in Liquidtight Flexible Metal Conduit (LFMC) (Based on Table 1, Chapter 9)

NEC Article 430 Part VII covers

[View Full Width]

[*] Types RHH, RHW, and RHW-2 without outer covering.

Fixture Wires

Type

Conductor size
(AWG/kcmil)

Metric Designator (Trade Size)

16
(½)

21
(¾)

27
(1)

35
(1¼)

41
(1½)

53
(2)

FFH-2,

18

8

15

24

42

54

89

RFH-2,

16

7

12

20

35

46

75

RFHH-3

             

SF-2,

18

11

19

30

53

69

113

SFF-2

16

9

15

25

44

57

93

 

14

7

12

20

35

46

75

SF-1,

18

19

33

53

94

122

199

SFF-1

             

RFH -1,

18

14

24

39

69

90

147

RFHH-2,

             

TF,TFF,

             

XF, XFF

             

RFHH-2,

16

11

20

32

56

72

119

TF,TFF,

             

XF, XFF

             

XF,XFF

14

9

15

25

44

57

93

TFN,

18

23

39

63

111

144

236

TFFN

16

17

30

48

85

110

180

PF,PFF,

18

21

37

60

105

136

223

PGF,

16

16

29

46

81

105

173

PGFF,

14

12

21

35

61

79

129

PAF,

             

PTF,

             

PTFF,

             

PAFF

             

HF,HFF,

18

28

48

77

136

176

288

ZF,ZFF,

16

20

35

57

100

129

212

ZHF

14

15

26

42

73

95

156

KF-2,

18

40

70

112

197

255

418

KFF-2

16

28

49

79

139

180

295

 

14

19

34

54

95

123

202

 

12

13

23

37

65

85

139

 

10

9

15

25

44

57

93

KF-1,

18

48

83

134

235

304

499

KFF-1

16

34

58

94

165

214

350

 

14

23

39

63

111

144

236

 

12

15

26

42

73

95

156

 

10

10

17

27

48

62

102

XF,

12

5

8

13

23

30

50

XFF

10

3

6

10

18

23

39

Table C7(A). Maximum Number of Compact Conductors in Liquidtight Flexible Metal Conduit (LFMC) (Based on Table 1, Chapter 9)

NEC Article 430 Part VII covers

[View Full Width]

Table C8. Maximum Number of Conductors or Fixture Wires in Rigid Metal Conduit (RMC) (Based on Table 1, Chapter 9)

NEC Article 430 Part VII covers

[View Full Width]

[*] Types RHH, RHW, and RHW-2 without outer covering.

Fixture Wires

Type

Conductor Size (AWG/kcmil)

Metric Designator (Trade Size)

16
(½)

21
(¾)

27
(1)

35
(1¼)

41
(1½)

53
(2)

FFH-2,

18

8

15

24

42

57

94

RFH-2,

16

7

12

20

35

48

79

RFHH-3

             

SF-2,

18

11

19

31

53

72

118

SFF-2

16

9

15

25

44

59

98

 

14

7

12

20

35

48

79

SF-1,

18

19

33

54

94

127

209

SFF-1

             

RFH-1,

18

14

25

40

69

94

155

RFHH-2,

             

TF, TFF,

             

XF, XFF

             

RFHH-2,

16

11

20

32

56

76

125

TF, TFF,

             

XF, XFF

             

XF, XFF

14

9

15

25

44

59

98

TFN,

18

23

40

64

111

150

248

TFFN

16

17

30

49

84

115

189

PF, PFF,

18

21

38

61

105

143

235

PGF,

16

16

29

47

81

110

181

PGFF,

14

12

22

35

61

83

136

PAF, PTF,

             

PTFF,

             

PAFF

             

HF,

18

28

48

79

135

184

303

HFF, ZF,

16

20

36

58

100

136

223

ZFF, ZHF

14

15

26

42

73

100

164

KF-2,

18

40

71

114

197

267

439

KFF-2

16

28

50

80

138

188

310

 

14

19

34

55

95

129

213

 

12

13

23

38

65

89

146

 

10

9

15

25

44

59

98

KF-1,

18

48

84

136

235

318

524

KFF-1

16

34

59

96

165

224

368

 

14

23

40

64

111

150

248

 

12

15

26

42

73

100

164

 

10

10

17

28

48

65

107

XF,

12

5

8

13

23

32

52

XFF

10

3

6

10

18

25

41

Table C8(A). Maximum Number of Compact Conductors in Rigid Metal Conduit (RMC) (Based on Table 1, Chapter 9)

NEC Article 430 Part VII covers

[View Full Width]

Table C9. Maximum Number of Conductors or Fixture Wires in Rigid PVC Conduit, Schedule 80 (Based on Table 1, Chapter 9)

NEC Article 430 Part VII covers

[View Full Width]

[*] Types RHH, RHW, and RHW-2 without outer covering.

Fixture Wires

Type

Conductor Size (AWG/kcmil)

Metric Designator (Trade Size)

16
(½)

21
(¾)

27
(1)

35
(1¼)

41
(1½)

53
(2)

FFH-2,

18

6

11

19

34

47

79

RFH-2,

16

5

9

16

28

39

67

RFHH-3

             

SF-2,

18

7

14

24

43

59

100

SFF-2

16

6

11

20

35

49

82

 

14

5

9

16

28

39

67

SF-1,

18

13

25

42

76

105

177

SFF-1

             

RFH-1,

18

10

18

31

56

77

130

RFHH-2,

             

TF, TFF,

             

XF, XFF

             

RFHH-2,

16

8

15

25

45

62

105

TF, TFF,

             

XF, XFF

             

XF, XFF

14

6

11

20

35

49

82

TFN,

18

16

29

50

90

124

209

TFFN

16

12

22

38

68

95

159

PF, PFF,

18

15

28

47

85

118

198

PGF,

16

11

22

36

66

91

153

PGFF,

14

8

16

27

49

68

115

PAF,

             

PTF,

             

PTFF,

             

PAFF

             

HF, HFF,

18

19

36

61

110

152

255

ZF, ZFF,

16

14

27

45

81

112

188

ZHF

14

10

19

33

59

82

138

KF-2,

18

28

53

88

159

220

371

KFF-2

16

19

37

62

112

155

261

 

14

13

25

43

77

107

179

 

12

9

17

29

53

73

123

 

10

6

11

20

35

49

82

KF-1,

18

33

63

106

190

263

442

KFF-1

16

23

44

74

133

185

310

 

14

16

29

50

90

124

209

 

12

10

19

33

59

82

138

 

10

7

13

21

39

54

90

XF, XFF

12

3

6

10

19

26

44

 

10

2

5

8

15

20

34

Note 1: This table is for concentric stranded conductors only. For compact stranded conductors, Table C9(A) should be used.

Note 2: Two-hour fire-rated RHH cable has ceramifiable insulation, which has much larger diameters than other RHH wires. Consult manufacturer's conduit fill tables.

Table C9(A). Maximum Number of Compact Conductors in Rigid PVC Conduit, Schedule 80 (Based on Table 1, Chapter 9)

NEC Article 430 Part VII covers

[View Full Width]

Table C10. Maximum Number of Conductors or Fixture Wires in Rigid PVC Conduit, Schedule 40 and HDPE Conduit (Based on Table 1, Chapter 9)

NEC Article 430 Part VII covers

[View Full Width]

[*] Types RHH, RHW, and RHW-2 without outer covering.

Fixture Wires

Type

Conductor Size (AWG/kcmil)

Metric Designator (Trade Size)

16
(½)

21
(¾)

27
(1)

35
(1¼)

41
(1½)

53
(2)

FFH-2,

18

8

14

23

40

54

90

RFH-2,

16

6

12

19

33

46

76

RFHH-3

             

SF-2,

18

10

17

29

50

69

114

SFF-2

16

8

14

24

42

57

94

 

14

6

12

19

33

46

76

SF-1,

18

17

31

51

89

122

202

SFF-1

             

RFHH-2,

18

13

23

38

66

90

149

TF, TFF,

             

XF, XFF,

             

RFH-1

             

RFFH-2,

16

10

18

30

53

73

120

TF, TFF,

             

XF, XFF

             

XF, XFF

14

8

14

24

42

57

94

TFN,

18

20

37

60

105

144

239

TFFN

16

16

28

46

80

110

183

PF, PFF,

18

19

35

57

100

137

227

PGF,

16

15

27

44

77

106

175

PGFF,

14

11

20

33

58

79

131

PAF, PTF,

             

PTFF,

             

PAFF

             

HF, HFF,

18

25

45

74

129

176

292

ZF, ZFF,

16

18

33

54

95

130

216

ZHF

14

13

24

40

70

95

158

KF-2,

18

36

65

107

187

256

424

KFF-2

16

26

46

75

132

180

299

 

14

17

31

52

90

124

205

 

12

12

22

35

62

85

141

 

10

8

14

24

42

57

94

KF-1,

18

43

78

128

223

305

506

KFF-1

16

30

55

90

157

214

355

 

14

20

37

60

105

144

239

 

12

13

24

40

70

95

158

 

10

9

16

26

45

62

103

XF, XFF

12

4

8

12

22

30

50

 

10

3

6

10

17

24

39

Table C10(A). Maximum Number of Compact Conductors in Rigid PVC Conduit, Schedule 40 and HDPE Conduit (Based on Table 1, Chapter 9)

NEC Article 430 Part VII covers

[View Full Width]

Table C11. Maximum Number of Conductors or Fixture Wires in Type A, Rigid PVC Conduit (Based on Table 1, Chapter 9)

NEC Article 430 Part VII covers

[View Full Width]

[*] Types RHH, RHW, and RHW-#2 without outer covering.

Fixture Wires

Type

Conductor Size
(AWG/kcmil)

Metric Designator (Trade Size)

16
(½)

21
(¾)

27
(1)

35
(1¼)

41
(1½)

53
(2)

FFH-2,

18

10

18

30

48

64

100

RFH-2,

16

9

15

25

41

54

85

RFHH-3

             

SF-2,

18

13

22

37

61

81

127

SFF-2

16

11

18

31

51

67

105

 

14

9

15

25

41

54

85

SF-1,

18

23

40

66

108

143

224

SFF-1

             

RFH-1,

18

17

29

49

80

105

165

RFHH-2,

             

TF, TFF,

             

XF, XFF

             

RFHH-2,

16

14

24

39

65

85

134

TF, TFF,

             

XF, XFF

             

XF,XFF

14

11

18

31

51

67

105

TFN,

18

28

47

79

128

169

265

TFFN

16

21

36

60

98

129

202

PF,PFF,

18

26

45

74

122

160

251

PGF,

16

20

34

58

94

124

194

PGFF,

14

15

26

43

70

93

146

PAF,

             

PTF,

             

PTFF,

             

PAFF

             

HF, HFF,

18

34

58

96

157

206

324

ZF, ZFF,

16

25

42

71

116

152

239

ZHF

14

18

31

52

85

112

175

KF-2,

18

49

84

140

228

300

470

KFF-2

16

35

59

98

160

211

331

 

14

24

40

67

110

145

228

 

12

16

28

46

76

100

157

 

10

11

18

31

51

67

105

KF-1,

18

59

100

167

272

357

561

KFF-1

16

41

70

117

191

251

394

 

14

28

47

79

128

169

265

 

12

18

31

52

85

112

175

 

10

12

20

34

55

73

115

XF,XFF

12

6

10

16

27

35

56

 

10

4

8

13

21

28

44

Table C11(A). Maximum Number of Compact Conductors in Type A, Rigid PVC Conduit (Based on Table 1, Chapter 9)

NEC Article 430 Part VII covers

[View Full Width]

Table C12. Maximum Number of Conductors in Type EB, PVC Conduit (Based on Table 1, Chapter 9)

Conductors

Type

Conductor Size (AWG/kcmil)

Metric Designator (Trade Size)

53
(2)

78
(3)

91
(3½)

103
(4)

129
(5)

155
(6)

RHH,

14

53

119

155

197

303

430

RHW,

12

44

98

128

163

251

357

RHW-2

10

35

79

104

132

203

288

8

18

41

54

69

106

151

6

15

33

43

55

85

121

4

11

26

34

43

66

94

3

10

23

30

38

58

83

2

9

20

26

33

50

72

1

6

13

17

21

33

47

1/0

5

11

15

19

29

41

2/0

4

10

13

16

25

36

3/0

4

8

11

14

22

31

4/0

3

7

9

12

18

26

250

2

5

7

9

14

20

300

1

5

6

8

12

17

350

1

4

5

7

11

16

400

1

4

5

6

10

14

500

1

3

4

5

9

12

600

1

3

3

4

7

10

700

1

2

3

4

6

9

750

1

2

3

4

6

9

800

1

2

3

4

6

8

900

1

1

2

3

5

7

1000

1

1

2

3

5

7

1250

1

1

1

2

3

5

1500

0

1

1

1

3

4

1750

0

1

1

1

3

4

 

2000

0

1

1

1

2

3

TW

14

111

250

327

415

638

907

 

12

85

192

251

319

490

696

 

10

63

143

187

238

365

519

 

8

35

79

104

132

203

288

RHH[1],

14

74

166

217

276

424

603

RHW[1],

             

RHW-2[1],

             

THHW,

             

THW,

             

THW-2

             

RHH[1],

12

59

134

175

222

341

485

RHW[1],

10

46

104

136

173

266

378

RHW-2[1],

             

THHW,

             

THW

             

RHH[1],

8

28

62

81

104

159

227

RHW[1],

6

21

48

62

79

122

173

RHW-2[1],

4

16

36

46

59

91

129

TW,

3

13

30

40

51

78

111

THW,

2

11

26

34

43

66

94

THHW,

1

8

18

24

30

46

66

THW-2

1/0

7

15

20

26

40

56

2/0

6

13

17

22

34

48

3/0

5

11

14

18

28

40

4/0

4

9

12

15

24

34

250

3

7

10

12

19

27

300

3

6

8

11

17

24

350

2

6

7

9

15

21

400

2

5

7

8

13

19

500

1

4

5

7

11

16

600

1

3

4

6

9

13

700

1

3

4

5

8

11

750

1

3

4

5

7

11

800

1

3

3

4

7

10

900

1

2

3

4

6

9

1000

1

2

3

4

6

8

1250

1

1

2

3

4

6

1500

1

1

1

2

4

6

1750

1

1

1

2

3

5

 

2000

0

1

1

1

3

4

THHN,

14

159

359

468

595

915

1300

THWN,

12

116

262

342

434

667

948

THWN-2

10

73

165

215

274

420

597

8

42

95

124

158

242

344

6

30

68

89

114

175

248

4

19

42

55

70

107

153

3

16

36

46

59

91

129

2

13

30

39

50

76

109

1

10

22

29

37

57

80

1/0

8

18

24

31

48

68

2/0

7

15

20

26

40

56

3/0

5

13

17

21

33

47

4/0

4

10

14

18

27

39

250

4

8

11

14

22

31

300

3

7

10

12

19

27

350

3

6

8

11

17

24

400

2

6

7

10

15

21

 

500

1

5

6

8

12

18

THHN,

600

1

4

5

6

10

14

THWN,

700

1

3

4

6

9

12

THWN-2

750

1

3

4

5

8

12

 

800

1

3

4

5

8

11

 

900

1

3

3

4

7

10

 

1000

1

2

3

4

6

9

FEP,

14

155

348

454

578

888

1261

FEPB,

12

113

254

332

422

648

920

PFA,

10

81

182

238

302

465

660

PFAH,

8

46

104

136

173

266

378

TFE

6

33

74

97

123

189

269

 

4

23

52

68

86

132

188

 

3

19

43

56

72

110

157

 

2

16

36

46

59

91

129

PFA,

1

11

25

32

41

63

90

PFAH,

             

TFE

             

PFA,

1/0

9

20

27

34

53

75

PFAH,

2/0

7

17

22

28

43

62

TFE, Z

3/0

6

14

18

23

36

51

 

4/0

5

11

15

19

29

42

Z

14

186

419

547

696

1069

1519

12

132

297

388

494

759

1078

10

81

182

238

302

465

660

8

51

115

150

191

294

417

6

36

81

105

134

206

293

4

24

55

72

92

142

201

3

18

40

53

67

104

147

2

15

34

44

56

86

122

 

1

12

27

36

45

70

99

XHH,

14

111

250

327

415

638

907

XHHW,

12

85

192

251

319

490

696

XHHW-2,

10

63

143

187

238

365

519

ZW

8

35

79

104

132

203

288

6

26

59

77

98

150

213

4

19

42

56

71

109

155

3

16

36

47

60

92

131

2

13

30

39

50

77

110

XHH,

1

10

22

29

37

58

82

XHHW,

1/0

8

19

25

31

48

69

XHHW-2

2/0

7

16

20

26

40

57

3/0

6

13

17

22

33

47

4/0

5

11

14

18

27

39

250

4

9

11

15

22

32

300

3

7

10

12

19

28

350

3

6

9

11

17

24

400

2

6

8

10

15

22

500

1

5

6

8

12

18

600

1

4

5

6

10

14

700

1

3

4

6

9

12

750

1

3

4

5

8

12

800

1

3

4

5

8

11

900

1

3

3

4

7

10

1000

1

2

3

4

6

9

1250

1

1

2

3

5

7

1500

1

1

1

3

4

6

1750

1

1

1

2

4

5

 

2000

0

1

1

1

3

5

Note 1: This table is for concentric stranded conductors only. For compact stranded conductors, Table C12(A) should be used.

Note 2: Two-hour fire-rated RHH cable has ceramifiable insulation, which has much larger diameters than other RHH wires. Consult manufacturer's conduit fill tables.

[1] Types RHH, RHW, and RHW-2 without outer covering.

Table C12(A). Maximum Number of Compact Conductors in Type EB, PVC Conduit (Based on Table 1, Chapter 9)

Compact Conductors

Type

Conductor Size (AWG/kcmil)

Metric Designator (Trade Size)

53
(2)

78
(3)

91
(3½)

103
(4)

129
(5)

155
(6)

THW,

8

30

68

89

113

174

247

THW-2,

6

23

52

69

87

134

191

THHW

4

17

39

51

65

100

143

 

2

13

29

38

48

74

105

 

1

9

20

26

34

52

74

 

1/0

8

17

23

29

45

64

 

2/0

6

15

19

24

38

54

 

3/0

5

12

16

21

32

46

 

4/0

4

10

14

17

27

38

 

250

3

8

11

14

21

30

 

300

3

7

9

12

19

26

 

350

3

6

8

11

17

24

 

400

2

6

7

10

15

21

 

500

1

5

6

8

12

18

 

600

1

4

5

6

10

14

 

700

1

3

4

6

9

13

 

750

1

3

4

5

8

12

 

900

1

3

4

5

7

10

 

1000

1

2

3

4

7

9

THHN,

8

THWN,

6

34

77

100

128

196

279

THWN-2

4

21

47

62

79

121

172

 

2

15

34

44

57

87

124

 

1

11

25

33

42

65

93

 

1/0

9

22

28

36

56

79

 

2/0

8

18

23

30

46

65

 

3/0

6

15

20

25

38

55

 

4/0

5

12

16

20

32

45

 

250

4

10

13

16

25

35

 

300

4

8

11

14

22

31

 

350

3

7

9

12

19

27

 

400

3

6

8

11

17

24

 

500

2

5

7

9

14

20

 

600

1

4

6

7

11

16

 

700

1

4

5

6

10

14

 

750

1

4

5

6

9

14

 

900

1

3

4

5

7

10

 

1000

1

3

3

4

7

10

XHHW,

8

39

88

115

146

225

320

XHHW-2

6

29

65

85

109

167

238

 

4

21

47

62

79

121

172

 

2

15

34

44

57

87

124

 

1

11

25

33

42

65

93

 

1/0

9

22

28

36

56

79

 

2/0

8

18

24

30

47

67

 

3/0

6

15

20

25

38

55

 

4/0

5

12

16

21

32

46

 

250

4

10

13

17

26

37

 

300

4

8

11

14

22

31

 

350

3

7

10

12

19

28

 

400

3

7

9

11

17

25

 

500

2

5

7

9

14

20

 

600

1

4

6

7

11

16

 

700

1

4

5

6

10

14

 

750

1

3

5

6

9

13

 

900

1

3

4

5

7

10

 

1000

1

3

4

5

7

10

Definition: Compact stranding is the result of a manufacturing process where the standard conductor is compressed to the extent that the interstices (voids between strand wires) are virtually eliminated.


Page 19

This annex is not part of the requirements of the NFPA document but is included for informational purposes.

Selection of Conductors. In the following examples, the results are generally expressed in amperes (A). To select conductor sizes, refer to the 0 through 2000 Volt (V) ampacity tables of Article 310 and the rules of 310.15 that pertain to these tables.

Voltage. For uniform application of Articles 210, 215, and 220, a nominal voltage of 120, 120/240, 240, and 208Y/120 volts shall be used in calculating the ampere load on the conductor.

Fractions of an Ampere. Except where the calculations result in a major fraction of an ampere (0.5 or larger), such fractions are permitted to be dropped.

Power Factor. Calculations in the following examples are based, for convenience, on the assumption that all loads have the same power factor (PF).

Ranges. For the calculation of the range loads in these examples, Column C of Table 220.55 has been used. For optional methods, see Columns A and B of Table 220.55. Except where the calculations result in a major fraction of a kilowatt (0.5 or larger), such fractions are permitted to be dropped.

SI Units. For metric conversions, 0.093 m2 = 1 ft2 and 0.3048 m = 1 ft.

Article 90 Introduction

General

Wiring and Protection

Wiring Methods and Materials

Equipment for General Use

Special Occupancies

Special Equipment

  • Article 645 Information Technology Equipment

Special Conditions

Tables

Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

Annex D. Examples

  • Annex D. Examples
  • Example No. D1(a) One-Family Dwelling
  • Example No. D1(b) One-Family Dwelling
  • Example No. D2(a) Optional Calculation for One-Family Dwelling Heating Larger than Air Conditioning [See Section 220.82]
  • Example No. D2(b) Optional Calculation for One-Family Dwelling, Air Conditioning Larger than Heating [See 220.82(A) and 220.82(C)]
  • Example No. D2(c) Optional Calculation for One-Family Dwelling with Heat Pump(Single-Phase, 240/120-Volt Service) (See 220.82)
  • Example No. D3 Store Building
  • Example D3(a) Industrial Feeders in a Common Raceway
  • Example No. D4(a) Multifamily Dwelling
  • Example No. D4(b) Optional Calculation for Multifamily Dwelling
  • Example No. D5(a) Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D5(b) Optional Calculation for Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D6 Maximum Demand for Range Loads
  • Example No. D8 Motor Circuit Conductors, Overload Protection, and Short-Circuit and Ground-Fault Protection
  • Example No. D9 Feeder Ampacity Determination for Generator Field Control
  • Example No. D10 Feeder Ampacity Determination for Adjustable-Speed Drive Control [See 215.2, 430.24, 620.13, 620.14, 620.61, Tables 430.22(E), and 620.14]
  • Example No. D11 Mobile Home (See 550.18)
  • Example No. D12 Park Trailer (See 552.47)

Annex E. Types of Construction

  • Annex E. Types of Construction

show all menu


Page 20

The dwelling has a floor area of 1500 square feet exclusive of an unfinished cellar not adaptable for future use, unfinished attic, and open porches. Appliances are a 12-kW range and a 5.5-kW, 240-volt dryer. Assume range and dryer kW ratings equivalent to kVA ratings in accordance with Sections 220.54 and 220.55.

Calculated Load [See 220.40]

General lighting load: 1500 sq. ft. at 3 volt-amperes per sq. ft. = 4500 volt-amperes.

Minimum Number of Branch Circuits Required [See Sec-tion 210.11(A)]

General lighting load: 4500 volt-amperes ÷ 120 V = 37.5 A. This requires three 15-A, 2-wire or two 20-A, 2-wire circuits.

Small appliance load: two 2-wire, 20-A circuits [see 210.11(C)(1)].

Laundry load: one 2-wire 20-A circuit [see 210.11(C)(2)].

Bathroom branch circuit: One 2-wire, 20-A circuit (no additional calculation is required for this circuit) [see 210.11(C)(3)].

Minimum Size Feeder Required [See 220.40]

General lighting

4500 VA

Small appliance

3000 VA

Laundry

1500 VA

Total general light and small appliance

9000 VA

3000 volt-amperes at 100%

3000 VA

9000 VA - 3000 VA = 6000 volt-amperes at 35%

2100 VA

Net load

5100 VA

Range (see Table 220.55)

8000 VA

Dryer load (see Table 220.54)

5500 VA

Net calculated load

18,600 VA

Net calculated load for 120/240-volt 3-wire single-phase service or feeder

NEC Article 430 Part VII covers

Sections 230.42(B) and 230.79 require service conductors and disconnecting means rated not less than 100 amperes.

Calculation for Neutral for Feeder and Service

Lighting and small appliance load

5100 VA

Range: 8000 volt-amperes at 70% (see 220.61)

5600 VA

Dryer: 5500 volt-amperes at 70% (see 220.61)

3850 VA

Total

14,550 VA

Calculated Load for Neutral

NEC Article 430 Part VII covers

Article 90 Introduction

General

Wiring and Protection

Wiring Methods and Materials

Equipment for General Use

Special Occupancies

Special Equipment

  • Article 645 Information Technology Equipment

Special Conditions

Tables

Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

Annex D. Examples

  • Annex D. Examples
  • Example No. D1(a) One-Family Dwelling
  • Example No. D1(b) One-Family Dwelling
  • Example No. D2(a) Optional Calculation for One-Family Dwelling Heating Larger than Air Conditioning [See Section 220.82]
  • Example No. D2(b) Optional Calculation for One-Family Dwelling, Air Conditioning Larger than Heating [See 220.82(A) and 220.82(C)]
  • Example No. D2(c) Optional Calculation for One-Family Dwelling with Heat Pump(Single-Phase, 240/120-Volt Service) (See 220.82)
  • Example No. D3 Store Building
  • Example D3(a) Industrial Feeders in a Common Raceway
  • Example No. D4(a) Multifamily Dwelling
  • Example No. D4(b) Optional Calculation for Multifamily Dwelling
  • Example No. D5(a) Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D5(b) Optional Calculation for Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D6 Maximum Demand for Range Loads
  • Example No. D8 Motor Circuit Conductors, Overload Protection, and Short-Circuit and Ground-Fault Protection
  • Example No. D9 Feeder Ampacity Determination for Generator Field Control
  • Example No. D10 Feeder Ampacity Determination for Adjustable-Speed Drive Control [See 215.2, 430.24, 620.13, 620.14, 620.61, Tables 430.22(E), and 620.14]
  • Example No. D11 Mobile Home (See 550.18)
  • Example No. D12 Park Trailer (See 552.47)

Annex E. Types of Construction

  • Annex E. Types of Construction

show all menu


Page 21

Assume same conditions as Example No. D1(a), plus addition of one 6-ampere, 230-volt room air-conditioning unit and one 12-ampere, 115-volt room air-conditioning unit,* one 8-ampere, 115-volt rated waste disposer, and one 10-ampere, 120-volt rated dishwasher. See Article 430 for general motors and Article 440, Part VII, for air-conditioning equipment. Motors have nameplate ratings of 115 V and 230 V for use on 120-V and 240-V nominal voltage systems.

From Example No. D1(a), feeder current is 78 amperes (3-wire 240 volts).

 

Line A

Neutral

Line B

Amperes from Example No. D1(a)

78

61

78

One 230-V air conditioner

6

6

One 115-V air conditioner and 120-V dishwasher

12

12

10

One 115-V disposal

8

8

25% of largest motor (see 430.24)

3

2

2

Total amperes per line

99

83

104

Therefore, the service would be rated 110 A.

*(For feeder neutral, use largest of the two appliances for unbalance.)

Article 90 Introduction

General

Wiring and Protection

Wiring Methods and Materials

Equipment for General Use

Special Occupancies

Special Equipment

  • Article 645 Information Technology Equipment

Special Conditions

Tables

Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

Annex D. Examples

  • Annex D. Examples
  • Example No. D1(a) One-Family Dwelling
  • Example No. D1(b) One-Family Dwelling
  • Example No. D2(a) Optional Calculation for One-Family Dwelling Heating Larger than Air Conditioning [See Section 220.82]
  • Example No. D2(b) Optional Calculation for One-Family Dwelling, Air Conditioning Larger than Heating [See 220.82(A) and 220.82(C)]
  • Example No. D2(c) Optional Calculation for One-Family Dwelling with Heat Pump(Single-Phase, 240/120-Volt Service) (See 220.82)
  • Example No. D3 Store Building
  • Example D3(a) Industrial Feeders in a Common Raceway
  • Example No. D4(a) Multifamily Dwelling
  • Example No. D4(b) Optional Calculation for Multifamily Dwelling
  • Example No. D5(a) Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D5(b) Optional Calculation for Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D6 Maximum Demand for Range Loads
  • Example No. D8 Motor Circuit Conductors, Overload Protection, and Short-Circuit and Ground-Fault Protection
  • Example No. D9 Feeder Ampacity Determination for Generator Field Control
  • Example No. D10 Feeder Ampacity Determination for Adjustable-Speed Drive Control [See 215.2, 430.24, 620.13, 620.14, 620.61, Tables 430.22(E), and 620.14]
  • Example No. D11 Mobile Home (See 550.18)
  • Example No. D12 Park Trailer (See 552.47)

Annex E. Types of Construction

  • Annex E. Types of Construction

show all menu


Page 22

The dwelling has a floor area of 1500 square feet exclusive of an unfinished cellar not adaptable for future use, unfinished attic, and open porches. It has a 12-kW range, a 2.5-kW water heater, a 1.2-kW dishwasher, 9 kW of electric space heating installed in five rooms, a 5-kW clothes dryer, and a 6-ampere, 230-volt room air-conditioning unit. Assume range, water heater, dishwasher, space heating, and clothes dryer kW ratings equivalent to kVA.

Air conditioner kVA calculation is 6A x 230V ÷ 1000 = 1.38 kVA

This 1.38 kVA [Item 1 from 220.82(C)] is less than 40% of 9 kVA of separately controlled electric heat [Item 6 from 220.82(C)], so the 1.38 kVA need not be included in the service calculation.

General Load

 

1500 sq. ft. at 3 volt-amperes

4500 VA

Two 20-amp. appliance outlet circuits at 1500 volt-amperes each

3000 VA

Laundry circuit

1500 VA

Range (at nameplate rating)

12,000 VA

Water heater

2500 VA

Dishwasher

1200 VA

Clothes dryer

5000 VA

Total

29,700 VA

Application of Demand Factor [See 220.82(B)]

First 10 kVA of general load at 100%

= 10,000 VA

Remainder of general load at 40% (19.7 kVA x .4)

= 7880 VA

Total of general load

= 17,880 VA

9 kVA of heat at 40% (9000 VA x .4)

= 3600 VA

Total

= 21,480 VA

Calculated load for service size

NEC Article 430 Part VII covers

Therefore, the minimum service size would be 100 amperes in accordance with 230.42 and 230.79.

Feeder Neutral Load (per 220.61)

 

1500 sq. ft. at 3 volt-amperes

4500 VA

Three 20-amp. circuits at 1500 volt-amperes

4500 VA

Total

9000 VA

3000 volt-amperes at 100%

3000 VA

9000 VA - 3000 VA = 6000 volt-amperes at 35%

2100 VA

Subtotal

5100 VA

Range8 kVA at 70%

5600 VA

Clothes dryer5 kVA at 70%

3500 VA

Dishwasher

1200 VA

Total

15,400 VA

Calculated Load for Neutral

NEC Article 430 Part VII covers

Article 90 Introduction

General

Wiring and Protection

Wiring Methods and Materials

Equipment for General Use

Special Occupancies

Special Equipment

  • Article 645 Information Technology Equipment

Special Conditions

Tables

Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

Annex D. Examples

  • Annex D. Examples
  • Example No. D1(a) One-Family Dwelling
  • Example No. D1(b) One-Family Dwelling
  • Example No. D2(a) Optional Calculation for One-Family Dwelling Heating Larger than Air Conditioning [See Section 220.82]
  • Example No. D2(b) Optional Calculation for One-Family Dwelling, Air Conditioning Larger than Heating [See 220.82(A) and 220.82(C)]
  • Example No. D2(c) Optional Calculation for One-Family Dwelling with Heat Pump(Single-Phase, 240/120-Volt Service) (See 220.82)
  • Example No. D3 Store Building
  • Example D3(a) Industrial Feeders in a Common Raceway
  • Example No. D4(a) Multifamily Dwelling
  • Example No. D4(b) Optional Calculation for Multifamily Dwelling
  • Example No. D5(a) Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D5(b) Optional Calculation for Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D6 Maximum Demand for Range Loads
  • Example No. D8 Motor Circuit Conductors, Overload Protection, and Short-Circuit and Ground-Fault Protection
  • Example No. D9 Feeder Ampacity Determination for Generator Field Control
  • Example No. D10 Feeder Ampacity Determination for Adjustable-Speed Drive Control [See 215.2, 430.24, 620.13, 620.14, 620.61, Tables 430.22(E), and 620.14]
  • Example No. D11 Mobile Home (See 550.18)
  • Example No. D12 Park Trailer (See 552.47)

Annex E. Types of Construction

  • Annex E. Types of Construction

show all menu


Page 23

The dwelling has a floor area of 1500 square feet exclusive of an unfinished cellar not adaptable for future use, unfinished attic, and open porches. It has two 20-ampere small appliance circuits, one 20-ampere laundry circuit, two 4-kW wall-mounted ovens, one 5.1-kW counter-mounted cooking unit, a 4.5-kW water heater, a 1.2-kW dishwasher, a 5-kW combination clothes washer and dryer, six 7-ampere, 230-volt room air-conditioning units, and a 1.5-kW permanently installed bathroom space heater. Assume wall-mounted ovens, counter-mounted cooking unit, water heater, dishwasher, and combination clothes washer and dryer kW ratings equivalent to kVA.

Air Conditioning kVA Calculation

NEC Article 430 Part VII covers

Load Included at 100%

Air conditioning: Included below [See Item 1 in 220.82(C)]

Space heater: Omit [See Item 5 in 220.82(C)]

General Load

 

1500 sq. ft. at 3 volt-amperes

4500 VA

Two 20-amp. small appliance circuits at 1500 volt-amperes each

3000 VA

Laundry circuit

1500 VA

2 ovens

8000 VA

1 cooking unit

5100 VA

Water heater

4500 VA

Dishwasher

1200 VA

Washer/dryer

5000 VA

Total general load

32,800 VA

1st 10 kVA at 100%

10,000 VA

Remainder at 40% (22.8 kVA x .4 x 1000)

9,120 VA

Subtotal general load

19,120 VA

Air conditioning

10,080 VA

Total

29,200 VA

Calculated Load for Service

NEC Article 430 Part VII covers

Feeder Neutral Load (per 220.61)

Assume that the two 4-kVA wall-mounted ovens are supplied by one branch circuit, the 5.1-kVA counter-mounted cooking unit by a separate circuit.

1500 sq. ft. at 3 volt-amperes

4500 VA

Three 20-amp circuits at 1500 volt-amperes

4500 VA

Subtotal

9000 VA

3000 volt-amperes at 100%

3000 VA

9000 VA - 3000 VA = 6000 volt-amperes at 35%

2100 VA

Subtotal

5100 VA

Two 4-kVA ovens plus one 5.1-kVA cooking unit = 13.1 kVA.

Table 220.55 permits 55% demand factor or

NEC Article 430 Part VII covers

Subtotal from above

5100 VA

Ovens and cooking unit: 7200 VA x 70% for neutral load

5040 VA

Clothes washer/dryer - 5 kVA x 70% for neutral load

3500 VA

Dishwasher

1200 VA

Total

14,840 VA

Calculated Load for Neutral

NEC Article 430 Part VII covers

Article 90 Introduction

General

Wiring and Protection

Wiring Methods and Materials

Equipment for General Use

Special Occupancies

Special Equipment

  • Article 645 Information Technology Equipment

Special Conditions

Tables

Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

Annex D. Examples

  • Annex D. Examples
  • Example No. D1(a) One-Family Dwelling
  • Example No. D1(b) One-Family Dwelling
  • Example No. D2(a) Optional Calculation for One-Family Dwelling Heating Larger than Air Conditioning [See Section 220.82]
  • Example No. D2(b) Optional Calculation for One-Family Dwelling, Air Conditioning Larger than Heating [See 220.82(A) and 220.82(C)]
  • Example No. D2(c) Optional Calculation for One-Family Dwelling with Heat Pump(Single-Phase, 240/120-Volt Service) (See 220.82)
  • Example No. D3 Store Building
  • Example D3(a) Industrial Feeders in a Common Raceway
  • Example No. D4(a) Multifamily Dwelling
  • Example No. D4(b) Optional Calculation for Multifamily Dwelling
  • Example No. D5(a) Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D5(b) Optional Calculation for Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D6 Maximum Demand for Range Loads
  • Example No. D8 Motor Circuit Conductors, Overload Protection, and Short-Circuit and Ground-Fault Protection
  • Example No. D9 Feeder Ampacity Determination for Generator Field Control
  • Example No. D10 Feeder Ampacity Determination for Adjustable-Speed Drive Control [See 215.2, 430.24, 620.13, 620.14, 620.61, Tables 430.22(E), and 620.14]
  • Example No. D11 Mobile Home (See 550.18)
  • Example No. D12 Park Trailer (See 552.47)

Annex E. Types of Construction

  • Annex E. Types of Construction

show all menu


Page 24

Dwelling has a floor area of 2000 sq. ft. exclusive of an unfinished cellar not adaptable for future use, unfinished attic, and open porches. It has a 12-kW range, 4.5-kW water heater, a 1.2-kW dishwasher, a 5-kW clothes dryer, a 2 ½-ton (24-ampere) heat pump with 15-kW of back-up heat.

Heat Pump kVA Calculation

NEC Article 430 Part VII covers

This 5.76 kVA is less than 15 kVA of the backup heat; therefore, the heat pump load need not be included in the service calculation. [See 220.82(C).]

General Load

 

2000 sq. ft. at 3 volt-amperes

6000 VA

Two 20-ampere appliance outlet circuits at 1500 volt-amperes each

3000 VA

Laundry circuit

1500 VA

Range (at nameplate rating)

12,000 VA

Water heater

4500 VA

Dishwasher

1200 VA

Clothes dryer

5000 VA

Subtotal general load

33,200 VA

First 10 kVA of general load at 100%

= 10,000 VA

Remainder of general load at 40% (23,200 VA x 0.4)

= 9280 VA

Total net general load

= 19,280 VA

Heat Pump and Supplementary Heat[*]

240V x 24A = 5,760 VA

15-kW electric heat:

5760 VA + (15,000 VA x 65%) = 5.76 kVA + 9.75 kVA = 15.51 kVA

[*] If supplementary heat is not on at the same time as heat pump, heat pump kVA need not be added to total.

Totals:

 

Net general load

19,280 VA

Heat pump and supplementary heat

15,510 VA

Total

34,790 VA

Calculated Load for Service

NEC Article 430 Part VII covers

Therefore, this dwelling unit may be served by a 150-ampere service.

Article 90 Introduction

General

Wiring and Protection

Wiring Methods and Materials

Equipment for General Use

Special Occupancies

Special Equipment

  • Article 645 Information Technology Equipment

Special Conditions

Tables

Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

Annex D. Examples

  • Annex D. Examples
  • Example No. D1(a) One-Family Dwelling
  • Example No. D1(b) One-Family Dwelling
  • Example No. D2(a) Optional Calculation for One-Family Dwelling Heating Larger than Air Conditioning [See Section 220.82]
  • Example No. D2(b) Optional Calculation for One-Family Dwelling, Air Conditioning Larger than Heating [See 220.82(A) and 220.82(C)]
  • Example No. D2(c) Optional Calculation for One-Family Dwelling with Heat Pump(Single-Phase, 240/120-Volt Service) (See 220.82)
  • Example No. D3 Store Building
  • Example D3(a) Industrial Feeders in a Common Raceway
  • Example No. D4(a) Multifamily Dwelling
  • Example No. D4(b) Optional Calculation for Multifamily Dwelling
  • Example No. D5(a) Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D5(b) Optional Calculation for Multifamily Dwelling Served at 208Y/120 Volts, Three Phase
  • Example No. D6 Maximum Demand for Range Loads
  • Example No. D8 Motor Circuit Conductors, Overload Protection, and Short-Circuit and Ground-Fault Protection
  • Example No. D9 Feeder Ampacity Determination for Generator Field Control
  • Example No. D10 Feeder Ampacity Determination for Adjustable-Speed Drive Control [See 215.2, 430.24, 620.13, 620.14, 620.61, Tables 430.22(E), and 620.14]
  • Example No. D11 Mobile Home (See 550.18)
  • Example No. D12 Park Trailer (See 552.47)

Annex E. Types of Construction

  • Annex E. Types of Construction

show all menu


Page 25

A store 50 ft. by 60 ft., or 3000 sq. ft., has 30 ft. of show window. There are a total of 80 duplex receptacles. The service is 120/240-volt, single-phase 3-wire service. Actual connected lighting load, 8500 volt-amperes.

Calculated Load (See 220.40)

 

Noncontinuous Loads

 

Receptacle Load (see 220.44)

 

80 receptacles at 180 VA

14,400 volt-amperes

10,000 VA at 100%

10,000 volt-amperes

14,400 VA - 10,000 VA = 4400 VA at 50%

2200 volt-amperes

Subtotal

12,200 volt-amperes

Continuous Loads

 

General Lighting[*]

 

3000 sq. ft. at 3 volt-amperes per sq. ft.

9000 volt-amperes

Show Window Lighting Load

 

30 ft. at 200 volt-amperes per foot

6000 volt-amperes

Outside sign circuit 1200 volt- amperes [see 220.14(F)]

1200 volt-amperes

Subtotal

16,200 volt-amperes

Subtotal from noncontinuous

12,200 volt-amperes

Subtotal noncontinuous loads plus continuous loads

28,400 volt-amperes

[*] In the example, 125 percent of the actual connected lighting load (8500 VA x 1.25 = 10,625 VA) is less than 125 percent of the load from Table 220.12, so the minimum lighting load from Table 220.12 is used in the calculation. Had the actual lighting load been greater than the value calculated from Table 220.12, 125 percent of the actual connected lighting load would have been used.

Minimum Number of Branch Circuits Required

General Lighting: Branch circuits need only be installed to supply the actual connected load [see 221.11(B)].

8500 VA x 1.25 = 10,625 volt-amperes

 

10,625 volt-amperes ÷ 240 volts

 

= 44 amperes for 3-wire, 120/240 V

The lighting load would be permitted to be served by 2-wire or 3-wire, 15- or 20-ampere circuits with combined capacity equal to 44 amperes or greater for 3-wire circuits or 88 amperes or greater for 2-wire circuits. The feeder capacity as well as the number of branch-circuit positions available for lighting circuits in the panelboard must reflect the full calculated load of 9000 VA x 1.25 = 11,250 volt-amperes.

Show Window

6,000 VA x 1.25 = 7500 VA

 

7500 volt-amperes ÷ 240 volts

 

= 31 amperes for 3-wire, 120/240V

The show window lighting is permitted to be served by 2-wire or 3-wire circuits with a capacity equal to 31 amperes or greater for 3-wire circuits or 62 amperes or greater for 2-wire circuits.

Receptacles required by 210.62 are assumed to be included in the receptacle load above if these receptacles do not supply the show window lighting load.

Receptacles

Receptacle Load:

 

14,400 volt-amperes ÷ 240 volts

 

= 60 amperes for 3-wire, 120/240 V

The receptacle load would be permitted to be served by 2-wire or 3-wire circuits with a capacity equal to 60 amperes or greater for 3-wire circuits or 120 amperes or greater for 2-wire circuits.

Minimum Size Feeder (or Service) Overcurrent Protection [See 215.3 or Section 230.90]

Subtotal noncontinuous loads

12,200 volt-amperes

Subtotal continuous load @ 125%

 

16,200 VA x 1.25

20,250 volt-amperes

Total

32,450 volt-amperes

32,450 VA ÷ 240 volts = 135 amperes

The next higher standard size is 150 amperes (See 240.6).

Minimum Size Feeder (or Service Conductors) Required [See 215.2, 230.42(A)]

For 120/240-volt, 3-wire system: 32,450 volt-amperes ÷ 240 volts = 135 amperes.

Service or feeder conductor is 1/0 Cu per 215.3 and Table 310.16 (with 75°C terminations).


Page 26

An industrial multi-building facility has its service at the rear of its main building, and then provides 480Y/277-volt feeders to additional buildings behind the main building in order to segregate certain processes. The facility supplies its remote buildings through a partially enclosed access corridor that extends from the main switchboard rearward along a path that provides convenient access to services within 15 m (50 ft) of each additional building supplied. Two building feeders share a common raceway for approximately 45 m (150 ft) and run in the access corridor along with process steam and control and communications cabling. The steam raises the ambient temperature around the power raceway to as much as 35°C. At a tee fitting, the individual building feeders then run to each of the two buildings involved. The feeder neutrals are not connected to the equipment grounding conductors in the remote buildings. All distribution equipment terminations are listed as being suitable for 75°C connections.

Each of the two buildings has the following loads:

Lighting, 11,600 VA, comprised of electric-discharge luminaires connected at 277 V

Receptacles, 22 125-volt, 20 ampere receptacles on general-purpose branch circuits, supplied by separately derived systems in each of the buildings

1-Air compressor, 460 volt, three phase, 7.5 hp

1-Grinder, 460 volt, three phase, 1.5 hp

3-Welders, AC transformer type (nameplate: 23 amperes, 480 volts, 60 percent duty cycle)

3-Industrial Process Dryers, 480 volt, three phase, 15 kW each (assume continuous use throughout certain shifts)

Determine the overcurrent protection and conductor size for the feeders in the common raceway, assuming the use of XHHW-2 insulation (90°C):

Calculated Load {Note: For reasonable precision, volt ampere calculations are carried to three significant figures only; where converted to amperes, the results are rounded to the nearest ampere [see 220.5(B)]}.

Noncontinuous Loads

 

Receptacle Load (see 220.44)

 

22 receptacles at 180 VA

3,960 VA

Welder Load [see 630.11(A), Table 630.11(A)]

 

Each welder: 480V x 23A x 0.78

= 8,610 VA

All 3 welders: [see 630.11(B)]

 

(demand factors 100%, 100%, 85% respectively)

 

8,610 VA + 8,610 VA + 7,320 VA

= 24,500 VA

Subtotal, Noncontinuous Loads

28,500 VA

Motor Loads (see 430.24, Table 430.250)

 

Air compressor: 11 A x 480 V x

NEC Article 430 Part VII covers
3 =

9,150 VA

Grinder: 3 A x 480 V x

NEC Article 430 Part VII covers
3 =

2,490 VA

Largest motor, additional 25%:

2,290 VA

Subtotal, Motor Loads

13,900 VA

By using 430.24, the motor loads and the noncontinuous loads can be combined for the remaining calculation.

Subtotal for load calculations,

42,400 VA

Noncontinuous Loads

 

Continuous Loads

 

General Lighting

11,600 VA

3 Industrial Process Dryers 15 kW each

45,000 VA

Subtotal, Continuous Loads:

56,600 VA

Overcurrent protection (see 215.3)

The overcurrent protective device must accommodate 125% of the continuous load, plus the noncontinuous load:

Continuous load

56,600 VA

Noncontinuous load

42,400 VA

Subtotal, actual load (actual load in amperes:

99,000 VA

99,000 VA / (480V x

NEC Article 430 Part VII covers
3) = 119 A]

 

14,200 VA (25% of 56,400 VA) (See 215.3)

14,200 VA

Total VA

113,200 VA

Conversion to amperes using three significant figures: 113,400 VA / (480V x

NEC Article 430 Part VII covers
3) = 136 A

 

Minimum size overcurrent protective device: 136 A

 

Minimum standard size overcurrent protective device (see 240.6): 150 amperes

 

Where the overcurrent protective device and its assembly are listed for operation at 100 percent of its rating, a 125 ampere overcurrent protective device would be permitted. However, overcurrent protective device assemblies listed for 100 percent of their rating are typically not available at the 125-ampere rating. (See 215.3 Exception.)

Ungrounded Feeder Conductors

The conductors must independently meet requirements for (1) terminations, and (2) conditions of use throughout the raceway run.

Minimum size conductor at the overcurrent device termination [see 110.14(C) and 215.2(A)(1), using 75°C ampacity column in Table 310.16]: 1/0 AWG.

Minimum size conductors in the raceway based on actual load [see Article 100, Ampacity, and 310.15(B)(2)(a) and correction factors to Table 310.16]:

99,000 VA / 0.7 / 0.96 = 147,000 VA

(70% = 310.15(B)(2)(a)) & (0.96 = Correction factors to Table 310.16)

Conversion to amperes:

147,000 VA / (480V x images/ent/U221A.GIF border=0>3) = 177A

Note that the neutral conductors are counted as current-carrying conductors [see 310.15(B)(4)(c)] in the example because the discharge lighting has substantial nonlinear content. This requires a 2/0 AWG conductor based on the 90°C column of Table 310.16. Therefore, the worst case is given by the raceway conditions, and 2/0 AWG conductors must be used. If the utility corridor was at normal temperatures [(30°C (86°F)], and if the lighting at each building were supplied from the local separately derived system (thus requiring no neutrals in the supply feeders) the raceway result (99,000 VA / 0.8 = 124,000 VA; 124,000 VA / (480V x images/ent/U221A.GIF border=0>3) = 149 A, or a 1 AWG conductor @ 90°C) could not be used because the termination result (1/0 AWG based on the 75°C column of Table 310.16) would become the worst case, requiring the larger conductor.

In every case, the overcurrent protective device shall provide overcurrent protection for the feeder conductors in accordance with their ampacity as provided by this Code (see 240.4). A 90°C 2/0 AWG conductor has a Table 310.16 ampacity of 195 amperes. Adjusting for the conditions of use (35°C ambient temperature, 8 current-carrying conductors in the common raceway),

195 amperes x 0.96 x 0.7 = 131 A

The 150-ampere circuit breaker protects the 2/0 AWG feeder conductors, because 240.4(B) permits the use of the next higher standard size overcurrent protective device. Note that the feeder layout precludes the application of 310.15(A)(2) Exception.

Feeder Neutral Conductor (see 220.61)

Because 210.11(B) does not apply to these buildings, the load cannot be assumed to be evenly distributed across phases. Therefore the maximum imbalance must be assumed to be the full lighting load in this case, or 11,600 VA. (11,600 VA / 277V = 42 amperes.) The ability of the neutral to return fault current [see 250.32(B)(2)(2)] is not a factor in this calculation.

Although the neutral runs between the main switchboard and the building panelboard, likely terminating on a busbar at both locations, the busbar connections are part of listed devices and are not "separately installed pressure devices." Therefore 110.14(C)(2) does not apply, and the normal termination temperature limits apply. In addition, the listing requirement to gain exemption from the additional sizing allowance under continuous loading (see 215.3 Exception) covers not just the overcurrent protective device, but its entire assembly as well. Therefore, since the lighting load is continuous, the minimum conductor size is based on 1.25 x (11,600 VA/277V) = 52 amperes, to be evaluated under the 75°C column of Table 310.16. The minimum size of the neutral is 6 AWG. This size is also the minimum size required by 215.2(A)(1), because the minimum size equipment grounding conductor for a 150-ampere circuit, as covered in Table 250.122, is 6 AWG.